32/171
Siemens Building Technologies
Basic Documentation LMU54... / LMU64...
CC1P7494en
HVAC Products
3 Functions
07.11.2002
The room setpoint is obtained from the following tables :
HzA: Heating circuit of the LMU... (1 or 2) which is controlled by the main heating
circuit of the RU (RU1)
HzB: Heating circuit of the LMU... (1 or 2) which is controlled by the secondary heating
circuit of the RU (RU2)
Refer to «Configuration of the heating circuits».
Hz1 and Hz2 can also be simultaneously assigned to the RU1 or RU2 program.
Without the RU, HzA = Hz1 and HzB = Hz2
RU
QAA53 /
QAA73
Room
setpoint RU
active
RU1 active
for heating
circuit
RU2 active
for heating
circuit
Outside
sensor
Room setpoint HzA
Room setpoint HzB
Beliebig
No
–
–
Don’t care
(TrSmax) / 2
(TrSmax) / 2
Present
Yes
No
No
Don’t care
(TrSmax) / 2
(TrSmax) / 2
Present
Yes
No
Yes
Don’t care
(TrSmax) / 2
(TrSmax) / 2
Present
Yes
Yes
No
Don’t care
TrSet
(TrSmax) / 2
Present
Yes
Yes
Yes
Don’t care
TrSet
(TrSmax) / 2
RU
QAA53 /
QAA73
Room
setpoint RU
active
RU1 active
for heating
circuit
RU2 active
for heating
circuit
Outside
sensor
Room setpoint HzA
Room setpoint HzB
Don’t care
No
–
–
Not
present
(TrSmax) / 2
(TrSmax) / 2
Don’t care
No
–
–
Present
TrSollMmi
TrSollMmi
Present
Yes
No
No
Not
present
(TrSmax) / 2
(TrSmax) / 2
Present
Yes
No
Nein
Present
TrSollMmi
TrSollMmi
Present
Yes
No
Yes
Not
present
(TrSmax) / 2
(TrSmax) / 2
Present
Yes
No
Yes
Present
TrSollMmi
(TrSmax) / 2
Present
Yes
Yes
No
Not
present
TrSet
(TrSmax) / 2
Present
Yes
Yes
No
Present
TrSet
TrSollMmi
Present
Yes
Yes
Yes
Don’t care
TrSet
(TrSmax) / 2
Room setpoint
Note
Without HMI
With HMI AGU2.361 /
AGU2.362, AGU2.303