123/171
Siemens Building Technologies
Basic Documentation LMU54... / LMU64...
CC1P7494en
HVAC Products
10 Technical data
07.11.2002
•
External ignition module (X3-03)
- Voltage
AC 230 V +10 % -15 %
- Current
5 mA ... 0.5 A, cos
ϕ >
0.8
must still ignite at AC 175 V
- Max. cable length
3 m
With regard to switch-on and switch-off characteristics, every type of external
ignition module used must be approved by Siemens !
•
Integrated ignition module (X3-04)
- Min. sparking power / pulse
3 mJ at 2 k
Ω
- Max. sparking power / pulse
4 mJ at 2 k
Ω
in the range of 175 V ... 253 V
- Min. pulse sequence
10 Hz at 175 V
- Max. pulse sequence
25 Hz at 253 V
- Electric shock hazard
cannot be touched
- Open-circuit voltage
20 kV
- Max. no-load operation
30 s