Siemens Building Technologies
Basic Documentation LMU54... / LMU64...
CC1P7494en
HVAC Products
3 Functions
07.11.2002
Mandatory settings
No.
DPA no.
Parameter name
Function
Setting level
OEM
Installer
9
174
NqmodNenn
Speed at the design point
Installer
No
Yes
10
175
NqmodMin
Minimum speed in heating
operation
Installer
No
If required
11
188
NqmodMinBw
Minimum speed in DHW
operation
Installer
No
If required
12
181
TkSnorm
Maximum boiler temperature
setpoint
Installer
No
Yes
13
173
TiAussenNorm
Design outside temperature
at the design point
Installer
No
Yes
14
172
dTkTrNenn
Design differential
Installer
No
Yes
15
116
dTkTrMax
Maximum temperature
differential of
∆
T
control
OEM
Yes
If required
167
KpDt
Proportional coefficient
OEM
No
If required
168
TvDt
Derivative action time
OEM
No
If required
16
169
TnDt
Integral action time
OEM
–
If required
To ensure safe startup of the modulating pump, a start kick with the maximum pump
speed (QmodMin) is given for 10 seconds each time the pump is activated.
On completion of the start kick, the value calculated from the heat demand will be
adopted.
In normal heating operation, the pump runs at reduced speed (reduced volumetric flow)
for the greatest part of the operating time and the flow temperature will be appropriately
raised.
On the software side, both
∆
T limitation and
∆
T supervision can be switched on or off.
When the modulating pump is running, maximum limitation of the flow temperature
according to the adjusted value is always active.
In reduced operation, it is always the reduced (minimum) volumetric flow that is used, or
the
∆
T supervison is active.
If the
∆
T limitation and / or the
∆
T supervision are active, they also acts in this operating
mode. It then works the same way as in normal operation, the only difference being the
lower flow temperature level.
The modulation function of the pump is deactivated since the heating is shut down.
In order not to extend the heating up phase due to the reduced volumetric flow, the plant
is always heated up with the full volumetric flow «NqmodNenn» within the first 30
minutes after reduced operation (night setback) or after plant shutdown (night
shutdown).
Then, a change to the volumetric flow is made that was calculated according to the
current outside temperature.
Summary of all
∆
T
parameters
(cont’d)
Behavior in different
operating modes
Pump overrun
Normal operation
(heating operation)
Reduced (setback)
operation
Shutdown mode
Heating up phase