Siemens Building Technologies
Basic Documentation LMU54... / LMU64...
CC1P7494en
HVAC Products
3 Functions
07.11.2002
The plant components decisive for the DHW circuit’s compensation variant are the
following:
•
LPB clip-in OCI420...
•
The RU
•
The HMI
•
DHW sensor 1
LPB clip-in
DHW sensor 1
TbwIst1
RU
QAA73...
DHW setpoint
TempAnfoVeBw
DHW demand
Compensation
variant
DHW circuit
Not present or
DHW locked
Not present
Don’t care
TbwSmin
Locked
Locked
Not present or
DHW locked
Present
Not present
(
TbwSmax) / 2
Continuously or via
time switch 2)
Emergency operation
Not present or
DHW locked
Present
Present
TdhwSet
RU- DHW
RU-compensated
Present and DHW
released 1)
Not present
Don’t care
TbwSmin
(DHW heated by RVA)
LMU-internal DHW
heating locked
Locked
Present and DHW
released 1)
Present
Not present
TbwSollRva
RVA-DHW
RVA-compensated
Present and DHW
released 1)
Present
Present
TbwSollRva
RVA-DHW
RVA-compensated
LPB clip-in
DHW sensor 1
TbwIst1
RU
QAA73...
DHW setpoint
TempAnfoVeBw
DHW demand
Compensation
variant DHW circuit
Not present or
DHW locked
Not present
Don’t care
TbwSmin
Locked
Locked
Not present or
DHW locked
Present
Not present
TbwSollMmi
Continuously or via
time switch 2)
Fixed value control
Not present or
DHW locked
Present
Present
TdhwSet 3)
RU- DHW
RU-compensated
Not present or
DHW locked
Present
Present
TbwSollMmi 3)
RU- DHW
RU- / HMI-
compensated
Present and DHW
released 1)
Not present
Don’t care
TbwSmin
(DHW heated by RVA)
LMU-internal DHW
heating locked
Locked
Present and DHW
released 1)
Present
Not present
TbwSollRva
RVA-DHW
RVA-compensated
Present and DHW
released 1)
Present
Present
TbwSollRva
RVA-DHW
RVA-compensated
DHW circuit
Without HMI
With HMI AGU2.361 /
AGU2.362, AGU2.303