137/171
Siemens Building Technologies
Basic Documentation LMU54... / LMU64...
CC1P7494en
HVAC Products
12 Parameter list / legend of parameter bit fields LMU...
07.11.2002
No
Name
Group
Function
Range
No
QAA73
AGU2.310
Level
QAA73
AGU2.310
LevelNo
PC_Tool
Level
PC_Tool
Switch-on / -off thresholds
117 SdHzEin
Boiler
Switch-on differential of burner in heating mode
0.5 ... 32 K
523
Engineer
5
Installer
118 SdHzAusMin
Boiler
Minimum switch-off differential of burner in heating
mode
0.5 ... 32 K
524
Engineer
5
Installer
119 SdHzAusMax
Boiler
Maximum switch-off differential of burner in heating
mode
0.5 ... 32 K
525
Engineer
5
Installer
120 SdBwEin1
DHW
Switch-on differential of burner in DHW heating mode
(sensor 1)
0.5 ... 32 K
526
Engineer
5
Installer
121 SdBwAus1Min
DHW
Minimum switch-off differential of burner in DHW
heating mode (sensor 1)
-32 ... 32 K
527
Engineer
5
Installer
122 SdBwAus1Max
DHW
Maximum switch-off differential of burner in DHW
heating mode (sensor 1)
-32 ... 32 K
528
Engineer
5
Installer
123 SdBwEin2
DHW
Switch-on differential of burner in DHW heating mode
(sensor 2)
0.5 ... 32 K
529
Engineer
5
Installer
125 SdBwAus2Max
DHW
Maximum switch-off differential of burner in DHW
heating mode (sensor 2)
-32 ... 32 K
531
Engineer
5
Installer
323 Sd_RL_groesser_VL
Boiler (S) LT
Threshold switch-off temperature when comparing
boiler flow / return temperature (el. LT)
5 ... 20 K
3
OEM
(production)
Configuration
126 Sth1
Weather compens HC1
Heating curve slope heating circuit 1
1 ... 40
532
Enduser
6
Enduser
127 Sth2
Weather compens
AGU2.500
Heating curve slope heating circuit 2
1 ... 40
533
Enduser
6
Enduser
128 DtR1
Weather compens HC1
Room setpoint readjustment heating circuit 1
-31 ... 31 K
534
Enduser
5
Installer
129 DtR2
Weather compens
AGU2.500
Room setpoint readjustment heating circuit 2
-31 ... 31 K
535
Enduser
5
Installer
135 PhzMax
Heating mode
Maximum degree of modulation in heating mode
(LmodTL <= PhzMax <= LmodVL)
0 ... 100 %
541
Engineer
4
OEM service
137 NhzMax
Heating mode
Maximum speed at maximum output in heating mode
(maximum speed limitation)
0 ... 12750 rpm
536
Engineer
4
OEM service
144 PminHuKw
Boiler INFO value
Minimum boiler output in kW (Hu)
0 ... 65535 kW
542
Engineer
5
Installer
145 PmaxHuKw
Boiler INFO value
Maximum boiler output in kW (Hu)
0 ... 65535 kW
543
Engineer
5
Installer
175 NqmodMin
PWM pump
Minimum pump speed permitted for the heating plant
10 ... 100 %
538
Engineer
5
Installer
188 NqmodMinBw
PWM pump
Minimum pump speed for full charging of stratification
storage tank
10 ... 100 %
539
Engineer
5
Installer
174 NqmodNenn
PWM pump
Pump speed at the heating plant's design point
1 ... 50
537
Engineer
5
Installer
180 QmodDrehzStufen
PWM pump
Number of speeds of modulating pump (supplier
specification)
2 ... 50
540
OEM
4
OEM service
146 QmodMin
PWM pump
Minimum degree of modulation of modulating pump
(supplier specification)
0 ... 70 %
548
OEM
4
OEM service
147 QmodMax
PWM pump
Maximum degree of modulation of modulating pump
(supplier specification)
10 ... 100 %
549
OEM
4
OEM service
435 Klambda1
PWM pump
Filter time constant of actual values of flow / return
temperature of dT control
0 ... 1
586
OEM
4
OEM service
148 Kon
Heating mode
Constant for quick setback without room influence
0 ... 20
551
Engineer
5
Installer
179 KtAbtastDt
PWM pump
Sampling factor of dT control
(as a factor for TabtastK)
0 ... 50
550
OEM
4
OEM service
149 HydrSystem
Boiler
Hydraulic system adjustment
0 ... 255
552
Engineer
5
Installer
193 KonfigHks
Heating mode
Configuration of heating circuits
0 ... 255
553
Engineer
5
Installer
194 KonfigRg0
Boiler
Setting flags: status code open-circuit sensor for Anx
channel suppressed / not suppressed
0 ... 255
554
Engineer
4
OEM service
150 KonfigRg1
Boiler
Setting flags
0 ... 255
555
Engineer
6
Enduser
151 KonfigRg2
DHW-inst DHW heater
Instantaneous DHW heater setting flags
0 ... 255
556
Engineer
5
Installer
152 KonfigRg3
Boiler
AD converter configuration and heating demand
0 ... 255
557
Engineer
5
Installer
153 KonfigRg4
Boiler
Setting flags
0 ... 255
558
Engineer
5
Installer
154 KonfigRg5
Boiler
Setting flags
0 ... 255
559
OEM
4
OEM service
155 KonfigRg6
Boiler
Setting flags
0 ... 255
560
OEM
4
OEM service
182 KonfigRg7
Boiler
Setting flags
0 ... 255
561
Engineer
5
Installer
328 KonfigRg8
DHW-inst DHW heater
Setting flags for instantaneous DHW heater
0 ... 255
587
Engineer
5
Installer
427 dTzapfEnde
DHW-inst DHW heater
Response threshold for detection of DHW consumption
with instantaneous DHW heater
-2 ... 1,984375 K/s
599
Engineer
5
Installer
428 dTzapfKomf
DHW-inst DHW heater
Response threshold for detection of DHW consumption
with instantaneous DHW heater in Comfort mode
-2 ... 1,984375 K/s
600
Engineer
5
Installer
429 dTzapfHz
DHW-inst DHW heater
Response threshold for detection of DHW consumption
with instantaneous DHW heater in heating mode
-2 ... 1,984375 K/s
601
Engineer
5
Installer
433 LmodRgVerz
Boiler
Output during controller delay time
(LmodTL <= LmodRgVerz <= LmodVL)
0 ... 100 %
598
Engineer
5
Installer
439 ZeitKoLrelGedStand
Boiler OCI420
Time constant for filtering the relative burner output
delivered via LPB bus
0 ... 2550 s
3
OEM
(production)
440 Kalibrationsfaktor
Boiler OCI420
Calibration of LMU for load signal delivered via LPB to
match effective output
-128 ... 127
3
OEM
(production)
470 KonfigEingang
Boiler
Progr input LMU basis
0 ... 255
614
Engineer
5
Installer
Switching differentials
Controller functions