7SR220 Settings Guide
Unrestricted Page 100 of 107
© 2013 Siemens Protection Devices Limited
Description
Range
Default
Hand Reset Outputs
Relays selected, as Hand Reset will remain latched until
manually reset from front panel or via communications link or
by removing DC Supply. By default relays are Self Resetting
and will reset when the driving signal is removed.
Combination of ( 1, 2, 3, 4, 5, 6, 7,
8, 9, 10, 11, 12, 13, 14 )
--------------
Min Operate Time 1
Minimum operate time of output relay if set to self reset, if also
set to be pulsed then this is the pulse width
0, 0.01 ... 59, 60
0.1 s
Min Operate Time 2
Minimum operate time of output relay 2 if set to self reset, if
also set to be pulsed then this is the pulse width
0, 0.01 ... 59, 60
0.1 s
Min Operate Time 3
Minimum operate time of output relay 3 if set to self reset, if
also set to be pulsed then this is the pulse width
0, 0.01 ... 59, 60
0.1 s
Min Operate Time 4
Minimum operate time of output relay 4 if set to self reset, if
also set to be pulsed then this is the pulse width
0, 0.01 ... 59, 60
0.1 s
Min Operate Time 5
Minimum operate time of output relay 5 if set to self reset, if
also set to be pulsed then this is the pulse width
0, 0.01 ... 59, 60
0.1 s
Min Operate Time 6
Minimum operate time of output relay 6 if set to self reset, if
also set to be pulsed then this is the pulse width
0, 0.01 ... 59, 60
0 s
Min Operate Time 7
Minimum operate time of output relay 7 if set to self reset, if
also set to be pulsed then this is the pulse width
0, 0.01 ... 59, 60
0 s
Min Operate Time 8
Minimum operate time of output relay 8 if set to self reset, if
also set to be pulsed then this is the pulse width
0, 0.01 ... 59, 60
0 s
Min Operate Time 9
Minimum operate time of output relay 9 if set to self reset, if
also set to be pulsed then this is the pulse width
0, 0.01 ... 59, 60
0 s
Min Operate Time 10
Minimum operate time of output relay 10 if set to self reset, if
also set to be pulsed then this is the pulse width
0, 0.01 ... 59, 60
0.1 s
Min Operate Time 11
Minimum operate time of output relay 11 if set to self reset, if
also set to be pulsed then this is the pulse width
0, 0.01 ... 59, 60
0.1 s
Min Operate Time 12
Minimum operate time of output relay 12 if set to self reset, if
also set to be pulsed then this is the pulse width
0, 0.01 ... 59, 60
0.1 s
Min Operate Time 13
Minimum operate time of output relay 13 if set to self reset, if
also set to be pulsed then this is the pulse width
0, 0.01 ... 59, 60
0.1 s
Min Operate Time 14
Minimum operate time of output relay 14 if set to self reset, if
also set to be pulsed then this is the pulse width
0, 0.01 ... 59, 60
0.1 s
Pickup Outputs
Selects which outputs can operate because a pickup condition
exists
Combination of ( 1, 2, 3, 4, 5, 6, 7,
8, 9, 10, 11, 12, 13, 14 )
--------------
Pulsed Outputs
Selects which outputs are pulsed. The pulse width is set by
the Min Operate Time setting for each output
Combination of ( 1, 2, 3, 4, 5, 6, 7,
8, 9, 10, 11, 12, 13, 14 )
--------------
3.13.3.
LED Config
Description
Range
Default
Содержание Argus 7SR21
Страница 1: ...Energy Management 7SR21 7SR22 Argus Overcurrent Relay Reyrolle Protection Devices ...
Страница 2: ......
Страница 4: ...Contents 7SR11 and 7SR12 Page 2 of 2 2018 Siemens Protection Devices Limited ...
Страница 116: ...7SR210 Instrumentation Guide Unrestricted Page 4 of 12 2018 Siemens Protection Devices Limited 1 Function Diagram ...
Страница 117: ...7SR210 Instrumentation Guide Unrestricted 2018 Siemens Protection Devices Limited Page 5 of 12 2 Menu Structure ...
Страница 129: ...7SR210 Settings Guide Unrestricted 2018 Siemens Protection Devices Limited Page 5 of 61 1 Function Diagram ...
Страница 130: ...7SR210 Settings Guide Unrestricted Page 6 of 61 2018 Siemens Protection Devices Limited 2 Menu Structure ...
Страница 185: ...7SR210 Settings Guide Unrestricted 2018 Siemens Protection Devices Limited Page 61 of 61 ...
Страница 189: ...7SR220 Instrumentation Guide Page 4 of 20 2017 Siemens Protection Devices Limited 1 Function Diagram ...
Страница 190: ...7SR220 Instrumentation Guide 2017 Siemens Protection Devices Limited Page 5 of 20 2 Menu Structure ...
Страница 194: ...7SR220 Instrumentation Guide 2017 Siemens Protection Devices Limited Page 9 of 20 Frequency 0 000Hz ...
Страница 211: ...7SR220 Settings Guide Unrestricted Page 6 of 107 2013 Siemens Protection Devices Limited 1 Function Diagram ...
Страница 277: ...7SR220 Settings Guide Unrestricted Page 72 of 107 2013 Siemens Protection Devices Limited ...
Страница 382: ...7SR220 Technical Manual Chapter 4 Page 2 of 96 2017 Siemens Protection Devices Limited ...
Страница 386: ...7SR220 Technical Manual Chapter 4 Page 6 of 96 2017 Siemens Protection Devices Limited ...
Страница 398: ...7SR220 Technical Manual Chapter 4 Page 18 of 96 2017 Siemens Protection Devices Limited ...
Страница 414: ...7SR220 Technical Manual Chapter 4 Page 34 of 96 2017 Siemens Protection Devices Limited ...
Страница 466: ...7SR220 Technical Manual Chapter 4 Page 86 of 96 2017 Siemens Protection Devices Limited ...
Страница 468: ...7SR220 Technical Manual Chapter 4 Page 88 of 96 2017 Siemens Protection Devices Limited ...
Страница 470: ...7SR220 Technical Manual Chapter 4 Page 90 of 96 2017 Siemens Protection Devices Limited ...
Страница 472: ...7SR220 Technical Manual Chapter 4 Page 92 of 96 2017 Siemens Protection Devices Limited ...
Страница 643: ...Unrestricted ...