7SR210 Settings Guide
Unrestricted ©2018 Siemens Protection Devices Limited
Page 21 of 61
3.5.6.
Inrush Detector
Description
Range
Default
Gn 81HBL2 Element
Selects whether the phase inrush detector 81HBL2 is enabled
Disabled, Enabled
Disabled
Gn 81HBL2 Bias
Selects the bias method used for magnetising inrush. Phase –
Segregated, each phase blocks itself. Cross – Blocked, each phase can
block the operation of other phases. Sum - Of Squares, each phase
blocks itself using the square root of the sum of squares of the 2nd
harmonic.
Phase, Cross, Sum
Cross
Gn 81HBL2 Setting
The magnetising inrush detector operates when the 2nd harmonic current
exceeds a set percentage of the fundamental current
0.1, 0.11 ... 0.49, 0.5
0.2 xI
3.6.
Control & Logic
3.6.1.
Autoreclose Prot’n
Description
Range
Default
Gn 79 P/F Inst Trips
Selects which phase fault protection elements are classed as
Instantaneous elements and start an autoreclose sequence. These will be
blocked from operating during Delayed autoreclose sequences. See
autoreclose section of manual for detail of what elements can cause only
Delayed protection to be used.
Combination of ( 51-1, 51-2, 50-1,
50-2 )
----
Gn 79 E/F Inst Trips
Selects which earth fault protection elements are classed as
Instantaneous elements and start an autoreclose sequence. These will be
blocked from operating during Delayed autoreclose sequences. See
autoreclose section of manual for detail of what elements can cause only
Delayed protection to be used.
Combination of ( 51N-1, 51N-2,
50N-1, 50N-2, 51G-1, 51G-2, 50G-
1, 50G-2 )
--------
Gn 79 SEF Inst Trips
Selects which sensitive earth fault protection elements are classed as
Instantaneous elements and start an autoreclose sequence. These will be
blocked from operating during Delayed autoreclose sequences. See
autoreclose section of manual for detail of what elements can cause only
Delayed protection to be used.
Combination of ( 51SEF-1, 51SEF-
2, 50SEF-1, 50SEF-2 )
----
Gn 79 P/F Delayed Trips
Selects which phase fault protection are classed as Delayed elements,
any selected elements operating will start an autoreclose sequence.
Combination of ( 51-1, 51-2, 50-1,
50-2 )
51-1, 51-2, 50-1,
50-2
Gn 79 E/F Delayed Trips
Selects which earth fault protection are classed as Delayed elements,
any selected elements operating will start an autoreclose sequence.
Combination of ( 51N-1, 51N-2,
50N-1, 50N-2, 51G-1, 51G-2, 50G-
1, 50G-2 )
51N-1, 51N-2,
50N-1, 50N-2,
51G-1, 51G-2,
50G-1, 50G-2
Gn 79 SEF Delayed Trips
Selects which sensitive earth fault elements are classed as Delayed
elements, any selected elements operating will start an autoreclose
sequence.
Combination of ( 51SEF-1, 51SEF-
2, 50SEF-1, 50SEF-2 )
51SEF-1, 51SEF-
2, 50SEF-1,
50SEF-2
Gn 79 P/F HS Trips
Selects which phase fault elements are classed as High Set elements,
any selected elements operating will start an autoreclose sequence.
Combination of ( 50-1, 50-2 )
--
Gn 79 E/F HS Trips
Selects which earth fault elements are classed as High Set elements, any
selected elements operating will start an autoreclose sequence.
Combination of ( 50N-1, 50N-2,
50G-1, 50G-2 )
----
Содержание Argus 7SR21
Страница 1: ...Energy Management 7SR21 7SR22 Argus Overcurrent Relay Reyrolle Protection Devices ...
Страница 2: ......
Страница 4: ...Contents 7SR11 and 7SR12 Page 2 of 2 2018 Siemens Protection Devices Limited ...
Страница 116: ...7SR210 Instrumentation Guide Unrestricted Page 4 of 12 2018 Siemens Protection Devices Limited 1 Function Diagram ...
Страница 117: ...7SR210 Instrumentation Guide Unrestricted 2018 Siemens Protection Devices Limited Page 5 of 12 2 Menu Structure ...
Страница 129: ...7SR210 Settings Guide Unrestricted 2018 Siemens Protection Devices Limited Page 5 of 61 1 Function Diagram ...
Страница 130: ...7SR210 Settings Guide Unrestricted Page 6 of 61 2018 Siemens Protection Devices Limited 2 Menu Structure ...
Страница 185: ...7SR210 Settings Guide Unrestricted 2018 Siemens Protection Devices Limited Page 61 of 61 ...
Страница 189: ...7SR220 Instrumentation Guide Page 4 of 20 2017 Siemens Protection Devices Limited 1 Function Diagram ...
Страница 190: ...7SR220 Instrumentation Guide 2017 Siemens Protection Devices Limited Page 5 of 20 2 Menu Structure ...
Страница 194: ...7SR220 Instrumentation Guide 2017 Siemens Protection Devices Limited Page 9 of 20 Frequency 0 000Hz ...
Страница 211: ...7SR220 Settings Guide Unrestricted Page 6 of 107 2013 Siemens Protection Devices Limited 1 Function Diagram ...
Страница 277: ...7SR220 Settings Guide Unrestricted Page 72 of 107 2013 Siemens Protection Devices Limited ...
Страница 382: ...7SR220 Technical Manual Chapter 4 Page 2 of 96 2017 Siemens Protection Devices Limited ...
Страница 386: ...7SR220 Technical Manual Chapter 4 Page 6 of 96 2017 Siemens Protection Devices Limited ...
Страница 398: ...7SR220 Technical Manual Chapter 4 Page 18 of 96 2017 Siemens Protection Devices Limited ...
Страница 414: ...7SR220 Technical Manual Chapter 4 Page 34 of 96 2017 Siemens Protection Devices Limited ...
Страница 466: ...7SR220 Technical Manual Chapter 4 Page 86 of 96 2017 Siemens Protection Devices Limited ...
Страница 468: ...7SR220 Technical Manual Chapter 4 Page 88 of 96 2017 Siemens Protection Devices Limited ...
Страница 470: ...7SR220 Technical Manual Chapter 4 Page 90 of 96 2017 Siemens Protection Devices Limited ...
Страница 472: ...7SR220 Technical Manual Chapter 4 Page 92 of 96 2017 Siemens Protection Devices Limited ...
Страница 643: ...Unrestricted ...