7SR220 Settings Guide
Unrestricted Page 44 of 107
© 2013 Siemens Protection Devices Limited
Description
Range
Default
Gn 79 P/F Delayed Trips
Selects which phase fault protection are classed as Delayed
elements, any selected elements operating will start an
autoreclose sequence.
Combination of ( 51-1, 51-2, 51-3,
51-4, 50-1, 50-2, 50-3, 50-4 )
51-1, 51-2, 51-3,
51-4, 50-1, 50-2,
50-3, 50-4
Gn 79 E/F Delayed Trips
Selects which earth fault protection are classed as Delayed
elements, any selected elements operating will start an
autoreclose sequence.
Combination of ( 51N-1, 51N-2,
51N-3, 51N-4, 50N-1, 50N-2, 50N-
3, 50N-4, 51G-1, 51G-2, 51G-3,
51G-4, 50G-1, 50G-2, 50G-3, 50G-
4 )
51N-1, 51N-2,
51N-3, 51N-4,
50N-1, 50N-2,
50N-3, 50N-4,
51G-1, 51G-2,
51G-3, 51G-4,
50G-1, 50G-2,
50G-3, 50G-4
Gn 79 SEF Delayed Trips
Selects which sensitive earth fault elements are classed as
Delayed elements, any selected elements operating will start
an autoreclose sequence.
Combination of ( 51SEF-1, 51SEF-
2, 51SEF-3, 51SEF-4, 50SEF-1,
50SEF-2, 50SEF-3, 50SEF-4 )
51SEF-1,
51SEF-2,
51SEF-3,
51SEF-4,
50SEF-1,
50SEF-2,
50SEF-3,
50SEF-4
Gn 79 P/F HS Trips
Selects which phase fault elements are classed as High Set
elements, any selected elements operating will start an
autoreclose sequence.
Combination of ( 50-1, 50-2, 50-3,
50-4 )
----
Gn 79 E/F HS Trips
Selects which earth fault elements are classed as High Set
elements, any selected elements operating will start an
autoreclose sequence.
Combination of ( 50N-1, 50N-2,
50N-3, 50N-4, 50G-1, 50G-2, 50G-
3, 50G-4 )
--------
3.11.2.
Autoreclose Config
Description
Range
Default
Gn 79 Autoreclose
If disabled then all attempts to control the AR IN/OUT status
will fail and the AR will be permanently Out Of Service. When
enabled the AR IN/OUT state may be controlled via the
CONTROL MODE menu option, via Binary Input or via local
or remote communications.
Disabled, Enabled
Enabled
Gn 79 Num Shots
Selects the number of auto-reclose attempts before the
Autorecloser locks out
1, 2, 3, 4
1
Gn 79 Retry Enable
Selects whether the Retry close functionality is enabled
Disabled, Enabled
Disabled
Gn 79 Retry Attempts
Selects the number of retries allowed per shot
0, 1, 2, 3, 4, 5, 6, 7, 8, 9, 10
1
Gn 79 Retry Interval
Time delay between retries
0, 1 ... 599, 600
60 s
Gn 79 Reclose Blocked Delay
Specifies the maximum time that the Autorecloser can be
blocked before proceeding to the lockout state. (NOTE: The
block delay timer only starts after the Deadtime.)
0, 1 ... 599, 600
60 s
Gn 79 Sequence Fail Timer
Time before lockout occurs on an incomplete reclose
sequence. (i.e Trip & starter conditions have not been cleared
after Sequence Fail Time.)
0, 1 ... 599, 600
60 s
Gn 79 Sequence Co-ord
Selects whether Sequence co-ordination functionality is used
or not.
Disabled, Enabled
Enabled
Содержание Argus 7SR21
Страница 1: ...Energy Management 7SR21 7SR22 Argus Overcurrent Relay Reyrolle Protection Devices ...
Страница 2: ......
Страница 4: ...Contents 7SR11 and 7SR12 Page 2 of 2 2018 Siemens Protection Devices Limited ...
Страница 116: ...7SR210 Instrumentation Guide Unrestricted Page 4 of 12 2018 Siemens Protection Devices Limited 1 Function Diagram ...
Страница 117: ...7SR210 Instrumentation Guide Unrestricted 2018 Siemens Protection Devices Limited Page 5 of 12 2 Menu Structure ...
Страница 129: ...7SR210 Settings Guide Unrestricted 2018 Siemens Protection Devices Limited Page 5 of 61 1 Function Diagram ...
Страница 130: ...7SR210 Settings Guide Unrestricted Page 6 of 61 2018 Siemens Protection Devices Limited 2 Menu Structure ...
Страница 185: ...7SR210 Settings Guide Unrestricted 2018 Siemens Protection Devices Limited Page 61 of 61 ...
Страница 189: ...7SR220 Instrumentation Guide Page 4 of 20 2017 Siemens Protection Devices Limited 1 Function Diagram ...
Страница 190: ...7SR220 Instrumentation Guide 2017 Siemens Protection Devices Limited Page 5 of 20 2 Menu Structure ...
Страница 194: ...7SR220 Instrumentation Guide 2017 Siemens Protection Devices Limited Page 9 of 20 Frequency 0 000Hz ...
Страница 211: ...7SR220 Settings Guide Unrestricted Page 6 of 107 2013 Siemens Protection Devices Limited 1 Function Diagram ...
Страница 277: ...7SR220 Settings Guide Unrestricted Page 72 of 107 2013 Siemens Protection Devices Limited ...
Страница 382: ...7SR220 Technical Manual Chapter 4 Page 2 of 96 2017 Siemens Protection Devices Limited ...
Страница 386: ...7SR220 Technical Manual Chapter 4 Page 6 of 96 2017 Siemens Protection Devices Limited ...
Страница 398: ...7SR220 Technical Manual Chapter 4 Page 18 of 96 2017 Siemens Protection Devices Limited ...
Страница 414: ...7SR220 Technical Manual Chapter 4 Page 34 of 96 2017 Siemens Protection Devices Limited ...
Страница 466: ...7SR220 Technical Manual Chapter 4 Page 86 of 96 2017 Siemens Protection Devices Limited ...
Страница 468: ...7SR220 Technical Manual Chapter 4 Page 88 of 96 2017 Siemens Protection Devices Limited ...
Страница 470: ...7SR220 Technical Manual Chapter 4 Page 90 of 96 2017 Siemens Protection Devices Limited ...
Страница 472: ...7SR220 Technical Manual Chapter 4 Page 92 of 96 2017 Siemens Protection Devices Limited ...
Страница 643: ...Unrestricted ...