
7SR210 & 7SR220 Applications Guide
Page 34 of 48
©2018 Siemens Protection Devices Limited
4.1.2 Auto-Reclose Example 2 (Use of Quicklogic with AR)
TI
ME
Figure 4.1-2 Example of Logic Application
Requirement: The relay at location ‘A’ it is required to provide a reclose sequence of 2 Instantaneous followed by
2 delayed recloses. Where the fault current level is between the values ‘I1’ and ‘I2’ and the first trip is initiated
from the 51-1 (IDMT) element, the IDMT characteristic should trip the CB and lockout the auto-reclose.
Typical settings are:
CONTROL & LOGIC > AUTORECLOSE PROT’N:
79 P/F Inst Trips
: 50-1
79 P/F Delayed Trips
: 51-1
CONTROL & LOGIC > AUTORECLOSE CONFIG > P/F SHOTS
79 P/F Prot’n Trip 1
: Inst
79 P/F Prot’n Trip 2
: Inst
79 P/F Prot’n Trip 3
: Delayed
79 P/F Prot’n Trip 4
: Delayed
The above settings are suitable at values of fault current above ‘I2’ however were a fault to occur with a current
value between ‘I1’ and ‘I2’ this would be detected by the 51-1 element only. As
Prot’n Trip 1
=
Inst
then the relay
would trip and reclose whereas it is required to lockout for this occurrence.
To provide a lockout for the above faults an additional element 50-2 with identical settings to 50-1 is assigned as
a Delayed Trip and is used in conjunction with the Quick Logic feature i.e.
OUTPUT CONFIG>OUTPUT MATRIX:
51-1
=
V1
OUTPUT CONFIG>OUTPUT MATRIX:
50-2
=
V2
OUTPUT CONFIG>OUTPUT MATRIX:
E1
=
V3
CONTROL & LOGIC>QUICK LOGIC:
E1
=
V1.!V2
INPUT CONFIG>INPUT MATRIX:
79 Lockout
=
V3
Содержание Argus 7SR21
Страница 1: ...Energy Management 7SR21 7SR22 Argus Overcurrent Relay Reyrolle Protection Devices ...
Страница 2: ......
Страница 4: ...Contents 7SR11 and 7SR12 Page 2 of 2 2018 Siemens Protection Devices Limited ...
Страница 116: ...7SR210 Instrumentation Guide Unrestricted Page 4 of 12 2018 Siemens Protection Devices Limited 1 Function Diagram ...
Страница 117: ...7SR210 Instrumentation Guide Unrestricted 2018 Siemens Protection Devices Limited Page 5 of 12 2 Menu Structure ...
Страница 129: ...7SR210 Settings Guide Unrestricted 2018 Siemens Protection Devices Limited Page 5 of 61 1 Function Diagram ...
Страница 130: ...7SR210 Settings Guide Unrestricted Page 6 of 61 2018 Siemens Protection Devices Limited 2 Menu Structure ...
Страница 185: ...7SR210 Settings Guide Unrestricted 2018 Siemens Protection Devices Limited Page 61 of 61 ...
Страница 189: ...7SR220 Instrumentation Guide Page 4 of 20 2017 Siemens Protection Devices Limited 1 Function Diagram ...
Страница 190: ...7SR220 Instrumentation Guide 2017 Siemens Protection Devices Limited Page 5 of 20 2 Menu Structure ...
Страница 194: ...7SR220 Instrumentation Guide 2017 Siemens Protection Devices Limited Page 9 of 20 Frequency 0 000Hz ...
Страница 211: ...7SR220 Settings Guide Unrestricted Page 6 of 107 2013 Siemens Protection Devices Limited 1 Function Diagram ...
Страница 277: ...7SR220 Settings Guide Unrestricted Page 72 of 107 2013 Siemens Protection Devices Limited ...
Страница 382: ...7SR220 Technical Manual Chapter 4 Page 2 of 96 2017 Siemens Protection Devices Limited ...
Страница 386: ...7SR220 Technical Manual Chapter 4 Page 6 of 96 2017 Siemens Protection Devices Limited ...
Страница 398: ...7SR220 Technical Manual Chapter 4 Page 18 of 96 2017 Siemens Protection Devices Limited ...
Страница 414: ...7SR220 Technical Manual Chapter 4 Page 34 of 96 2017 Siemens Protection Devices Limited ...
Страница 466: ...7SR220 Technical Manual Chapter 4 Page 86 of 96 2017 Siemens Protection Devices Limited ...
Страница 468: ...7SR220 Technical Manual Chapter 4 Page 88 of 96 2017 Siemens Protection Devices Limited ...
Страница 470: ...7SR220 Technical Manual Chapter 4 Page 90 of 96 2017 Siemens Protection Devices Limited ...
Страница 472: ...7SR220 Technical Manual Chapter 4 Page 92 of 96 2017 Siemens Protection Devices Limited ...
Страница 643: ...Unrestricted ...