6 Operation
6.6 Examples for Parameterization
126
SICAM I/O Unit, 7XV5673, Device Manual
E50417-H1040-C484-A3, Edition 05.2012
6.6.6
Application as Contact Multiplier
Conceptual Formulation
✧
Parameterize the threshold value voltage of the binary input terminals N8/9 and change the name for the
binary input indication.
✧
Route the binary input terminals N8/9 to the 2 binary outputs (relay outputs) terminals N2/1 and N4/3 with
various modes.
✧
Parameterize the threshold value voltage of the binary input terminals P10/9 and change the name for the
binary input indication.
✧
Route the binary input terminals P10/9 to the 4 binary outputs (relay outputs) terminals N5/6/7, P2/1,
P4/3, and P5/6/7 with various modes.
✧
Use the hardware configuration according to Figure 5-5.
Setting of Binary Inputs
Figure 6-74
Binary Input Settings
NOTE
In order to be able to better identify the substation-specific identification of the messages, Siemens recom-
mends assigning individual names for the binary input indications. The default names set by the factory can
also be kept.
MAN_SICAM_IO-Unit_7XV5673_US.book Page 126 Thursday, May 10, 2012 10:59 AM