6 Operation
6.3 Configuration of the Device
93
SICAM I/O Unit, 7XV5673, Device Manual
E50417-H1040-C484-A3, Edition 05.2012
✧
Enter the VLAN priority (0 to 7) in the
VLAN Priority
field.
✧
Enter the time (1 ms to 500 ms) in the
Retransmit MIN
field.
✧
Enter the time (500 ms to 65,534 ms) in the
Retransmit MAX
field.
✧
If you do not want to change any further settings, continue with the
activation
of the device configuration
as described in “Activating the Parameter Set”. If you want to change further settings, enter these changes
and then enable the device configuration as described in “Activating the Parameter Set”.
Download ICD File
✧
Click the
Download ICD file
button.
The ICD file of the SICAM I/O Unit corresponding to the currently selected edition is downloaded.
No Ethernet Communication
✧
Select the
-none-
entry from the
Bus protocol
list box.
If you select
-none-
, no protocol will be available. In this case, click the
Send
button.
After having clicked the
Send
button, the parameters are transmitted to the device but not enabled yet
(passive parameter set).
If you do not want to change any further settings, continue with the
activation
of the device configuration
as described in “Activating the Parameter Set”. If you want to change further settings, enter these changes
and then enable the device configuration as described in “Activating the Parameter Set”.
6.3.3.7
IEC 61850 GOOSE Subscriber Configuration
The IEC 61850 IED configuration philosophy of the SICAM I/O Unit is to have one separate static ICD file each
for Edition 1 and Edition 2 of IEC 61850. For the substation configuration, these ICD files are imported into the
IEC 61850 system configurator (e.g. DIGSI 4).
When the configuration has been completed, the thus generated SCD file can be loaded into the SICAM I/O
Mapping Tool, and a binary IEC 61850 parameter set can be created (proprietary format).
The result can then be uploaded via the HTML page.
NOTE
After having selected the GOOSE publisher parameters, the device must be restarted.
NOTE
After having selected IEC 61850, the device must be restarted.
NOTE
The configuration requires the installation of the SICAM I/O Mapping Tool program (see chapter 4.8).