8 Communication
8.3 I/O Mirror
162
SICAM I/O Unit, 7XV5673, Device Manual
E50417-H1040-C484-A3, Edition 05.2012
Client
•
Communication status:
Startup 1: Start phase 1 has started
Startup 1 fail: Incorrect MLFB number
Startup 2: Start phase 2 has started
Startup 2 fail: Incorrect device configuration values
Data Exchange: Normal data exchange between client and
server
•
Transfer time:
Transfer time of a telegram cycle from client to server and
back
8.3.3.2
Ethernet Communication - I/O Server
Figure 8-9
Diagnosis Ethernet Communication - I/O Mirror Server
Parameter
•
Operating mode:
I/O mirror server
•
Port number:
51000
•
Communication supervision time:
Default: 80 ms
Counter
•
Received bytes:
Total number of received bytes via communication since the
last start of the device or since last deleting the counter
•
Sent bytes:
Total number of sent bytes via communication since the last
start of the device or since last deleting the counter
•
Good messages:
Total number of received frames, which were detected as
valid telegrams since the last start of the device or since last
deleting the counter
•
Bad messages:
Total number of telegram errors since the start of the device
or since last deleting the counter
MAN_SICAM_IO-Unit_7XV5673_US.book Page 162 Thursday, May 10, 2012 10:59 AM