12 Operational Indications
208
SICAM I/O Unit, 7XV5673, Device Manual
E50417-H1040-C484-A3, Edition 05.2012
Default IP Address
The IP-Addr. button has been
pressed for more than 3 s.
Indication on: IP-Addr. push-button was
pressed
The device restarts and applies the default IP
address.
Primary NTP Server Error
Faulty or no response from the
primary NTP server
Indication on: Error
Indication off: Valid time messages has been
received for a period of 10 min
Only for time synchronization via
Ethernet NTP (see chapter 6.3.3.5)
Secondary NTP Server Error
Faulty or no response from the
secondary NTP server
Indication on: Error
Indication off: Valid time messages has been
received for a period of 10 min
Only for time synchronization via
Ethernet NTP (see chapter 6.3.3.5)
Daylight Saving Time
Switching between daylight
saving time/standard time
Indication on: Daylight saving time
Indication off: Standard time
Ethernet Link Error
Ethernet connection error on
port 1 of the Ethernet switch
(without Y-cable available)
Indication on: Error
Indication off: Ethernet link recognized
Ethernet Link 2 Error
Ethernet connection error on
port 2 of the Ethernet switch
(available only with Y-cable)
Indication on: Error
Indication off: Ethernet link recognized
Modbus TCP OK
(Modbus TCP Server)
At least one Modbus TCP
connection has received Modbus
messages.
Indication on: At least one Modbus message
was received during the set monitoring time.
The time stamp is set when the first valid
message is received.
Indication off: No Modbus message was
received during the set monitoring time.
See chapter 6.3.3.6
Modbus Serial OK
(Modbus RTU Slave)
The Modbus serial
communication has received a
valid Modbus message.
Indication on: At least one serial message
was received during the set monitoring time.
The time stamp is set when the first valid
message is received.
Indication off: No serial message was
received during the set monitoring time.
See chapter 6.3.3.8
Settings Load
Starting to change the
parameters of the passive
parameter set.
Indication on: Start of changes
Indication off: Changes complete
Indication
(Relevant for Operating Mode)
Description
Notes