11 Technical Data
11.2 Test Data
201
SICAM I/O Unit, 7XV5673, Device Manual
E50417-H1040-C484-A3, Edition 05.2012
11.1.5
General Data
11.2
Test Data
11.2.1
Electrical Tests
Standards
Insulation Test
Battery
Type
PANASONIC CR2032 or
VARTA 6032 101 501
Voltage
3 V
Capacity
230 mAh
Typical life
10 years
In operation with continuous supply voltage
2 months within 10 years
In operation where supply voltage is not
applied continuously
Protection class
DIN rail side
IP20
Terminal side (terminals)
IP20
Top side
IP20
Standards:
IEC 60255
IEEE Std C37.90, see individual functions
VDE 0435
For more standards see also individual functions
Standards:
IEC 60255-27 and IEC 60870-2-1
Voltage test (routine test) of
- auxiliary voltage
- binary inputs and relay outputs
DC 3.6 kV
AC 3.25 kV, 50 Hz
Voltage test (routine test) of isolated communication
ports only
- J (RS485)
- Z (Ethernet)
AC 500 V, 50 Hz
DC 700 V
Impulse voltage test (type test) of all process cir-
cuits (except for communication ports) against the
internal electronics
6 kV (peak value);
1.2 µs/50 µs; 0.5 J;
3 positive and 3 negative impulses at intervals of 1 s
Impulse voltage test (type test) of all process cir-
cuits against each other (except for communication
ports) and against the PE terminal of class III
5 kV (peak value);
1.2 µs/50 µs; 0.5 J;
3 positive and 3 negative impulses at intervals of 1 s
MAN_SICAM_IO-Unit_7XV5673_US.book Page 201 Thursday, May 10, 2012 10:59 AM