13 Operating Parameters
13.2 Administrative
217
SICAM I/O Unit, 7XV5673, Device Manual
E50417-H1040-C484-A3, Edition 05.2012
13.2.3
Ethernet Communication
Additional parameters if the source is Ethernet NTP
Primary NTP server IP
Address
192.168.0.254
Any
Secondary NTP server IP
Address
192.168.0.253
Any
Error indication after
10 min
2 min to 120 min
Additional parameters if source is fieldbus (Modbus RTU)
Error indication after
10 min
2 min to 120 min
Parameter
Default Setting
Setting Ranges
IP Address
1)
192.168.0.55
Any, 0.0.0.0 for DHCP
Subnet mask
1)
255.255.255.0
Any
Default gateway
1)
192.168.0.1
Any
Bus protocol/Operating mode
Modbus TCP
-none-
Modbus TCP
Modbus UDP
I/O Mirror client
I/O Mirror server
IEC 61850
Modbus TCP
Use a user-port number
2)
no
no
yes
User-port number
2)
10000
10000 to 65535
Access rights for user port
Full
Full
Read only
Access rights for user port 502
Full
Full
Read only
Keep Alive time
10 s
0 s = switch off
1 s to 65 535 s
Communication supervision time
600 * 100 ms
0 s = none
100 ms to 6 553 400 ms
Modbus UDP
Port number
51000
10000 to 65535
Access rights
Full
Full
Read only
Communication supervision time
8 * 10 ms
0 ms = invalid
10 ms to 60 000 ms
I/O Mirror Client
(can only be parameterized, if no I/O mirror mode is selected under Serial Communication)
Server IP address
192.168.0.56
Any
Server port
51000
10000 to 65535