13 Operating Parameters
13.1 Process Connections
214
SICAM I/O Unit, 7XV5673, Device Manual
E50417-H1040-C484-A3, Edition 05.2012
13.1
Process Connections
13.1.1
Binary Inputs
13.1.2
Binary Outputs (Relay Outputs)
Parameter
Default Setting
Setting Range
Threshold value voltage
can be set for all binary inputs individually
19 V
19 V
88 V
176 V
Software filter time
can be set for each terminal block individually
1 (*2) ms
2 ms to 120 000 ms
Binary input indication
can be set for all binary inputs individually
For example for Terminals P8/9:
Binary input 1 - Terminal block P
Arbitrary text; name of
the indication
Parameter
Default Setting
Settings
Indication
(can be set individually for all relay outputs)
-none-
-none-
Device OK
Battery Failure
Settings Load
Settings Check
Settings Activate
Modbus TCP OK
Ethernet Link Error
Modbus Serial OK
Time Synchronization Error
Primary NTP Server Error
Secondary NTP Server Error
Daylight Saving Time
Ethernet Link 2 Error
Default IP Address
Indication 1 from Remote
Indication 2 from Remote
Indication 3 from Remote
Indication 4 from Remote
Indication 5 from Remote
Indication 6 from Remote
Binary In 1 - Terminal block N
Binary In 2 - Terminal block N
Binary In 3 - Terminal block N
Binary In 1 - Terminal block P
Binary In 2 - Terminal block P
Binary In 3 - Terminal block P
I/O Ethernet OK
I/O Ethernet Fail > 0.05 %
I/O Serial OK
I/O Serial Fail > 0.05 %
I/O Mirror OK
Invert source
(can be set individually for all relay outputs)
no
no
yes
Operating mode
(can be set individually for all relay outputs)
Persistent
Persistent
Persistent with fail safe
Pulse
Pulse with retrigger
MAN_SICAM_IO-Unit_7XV5673_US.book Page 214 Thursday, May 10, 2012 10:59 AM