6 Operation
6.3 Configuration of the Device
85
SICAM I/O Unit, 7XV5673, Device Manual
E50417-H1040-C484-A3, Edition 05.2012
Protocol Modbus UDP
Figure 6-33
Configure Tab, Communication Ethernet via Modbus UDP Input/Output Window
✧
Enter the port number (
≥
10000) into the
Port number
field.
✧
Under
Access rights
you can select either the
Full
access rights or
Read only
authorization.
✧
Enter the time in x
* 10 ms
into the
Communication supervision time
field..
✧
Click the
Send
button.
After clicking the
Send
button, the parameters are transmitted to the device but not enabled yet (passive
parameter set).
✧
If you do not want to change any other settings, continue with the
Activation
of the device configuration
according to chapter 6.3.1.3. If you want to change other settings, enter the changes and then enable the
device configuration.