6 Operation
6.3 Configuration of the Device
88
SICAM I/O Unit, 7XV5673, Device Manual
E50417-H1040-C484-A3, Edition 05.2012
Ethernet Communication Using the IEC 61850 Bus Protocol
✧
Select the
IEC 61850
entry from the
Bus protocol
list box.
✧
The
Communication Ethernet
input/output window with
Bus protocol IEC 61850
opens.
Figure 6-36
Configure Tab, Ethernet Communication via IEC 61850 Input/Output Window
✧
Select
Edition 1
or
Edition 2
from the
IEC 61850 Edition
list box.
NOTE
When selecting IEC 61850 (and restarting the device), the IEC 61850 server and GOOSE are started.
After having selected IEC 61850, the device must be restarted.
NOTE
The device behaves as defined in the respective edition.
After having clicked the
Download ICD file
button, the ICD file that corresponds to the selected edition is down-
loaded.
NOTE
Before uploading the Subscriber configuration, please make sure that the
has been executed. For uploading the Subscriber configuration, the MAP file (file extension
.MAP) is required.
MAN_SICAM_IO-Unit_7XV5673_US.book Page 88 Thursday, May 10, 2012 10:59 AM