6 Operation
6.3 Configuration of the Device
83
SICAM I/O Unit, 7XV5673, Device Manual
E50417-H1040-C484-A3, Edition 05.2012
To change the Ethernet communication, proceed as follows:
✧
In the navigation window, select the
Operational
menu, then the
Administrative
submenu and click
Communication Ethernet
.
The
Communication Ethernet
input/output window opens.
Figure 6-32
Configure Tab, Communication Ethernet via Modbus TCP Input/Output Window
✧
Enter the IP address into the
IP address
field.
✧
Enter the subnet mask into the
Subnet mask
field.
✧
Enter the gateway into the
Default gateway
field.
✧
If you want to switch on the Ethernet switch, select the option
yes
in the option field
Ethernet switch on
.
✧
Select the desired
Bus protocol,
the
desired
Operating mode
or
-none-
from the
Bus protocol/
Operating mode
list box.
If you select
-none-
, there will be no log and no mode available. In this case, click the
Send
button. If you
have selected a
Modbus
protocol or an
Operating mode
, parameterize as follows:
NOTE
When the network settings have been changed and the changed parameters have been activated (see descrip-
tion below), the device automatically perform a restart.
NOTE
The Ethernet switch is switched off at delivery to ensure a correct operation of the I/O mirror of 2 devices without
Y-cable. Only switch on the Ethernet switch (option
yes
), if you connect a Y-cable at the Ethernet connector.