6 Operation
6.3 Configuration of the Device
86
SICAM I/O Unit, 7XV5673, Device Manual
E50417-H1040-C484-A3, Edition 05.2012
I/O Mirror Client
Figure 6-34
Configure Tab, Communication Ethernet via I/O mirror Client Input/Output Window
✧
Enter the server IP address into the
Server IP address
field.
✧
Enter the port number (
≥
10000) into the
Server port
field.
✧
Enter the response time under
Response timeout
.
Siemens recommends the factory setting.
✧
Click the
Send
button.
After clicking the
Send
button, the parameters are transmitted to the device but not enabled yet (passive
parameter set).
✧
If you do not want to change any other settings, continue with the
Activation
of the device configuration
according to chapter 6.3.1.3. If you want to change other settings, enter the changes and then enable the
device configuration.
NOTE
Can only be parameterized, if no
I/O mirror mode
is selected under
Communication Serial
.