Possible pins for the connection are highlighted.
Safety Designer checks for any restrictions that may apply. For example, an OSSD
cannot be placed on an input.
b
Drop the signal on the pin.
✓
The signal name is shown on the right next to the pins.
Removing signals
b
Click on the signal.
b
Drag the signal on to the trash-can symbol.
✓
The pins are free again.
7.13.1
Outputs
Contamination
Signals that the optics cover is contaminated.
•
Partial contamination, optical cover should be cleaned soon (contamination warning).
setting:
The optics cover needs to be cleaned soon.
•
Switch the safety laser scanner to the OFF state in the event of severe contamination (contami‐
nation error).
setting: All safety outputs in the OFF state. The optics cover is severely
contaminated and must be cleaned immediately.
Error
Signals an error.
•
Device error
setting: Device errors are serious errors where all safety outputs switch
to the OFF state and the device switches to the locking state. Once the cause of
the error has been rectified, the device must be completely restarted.
•
Application error
setting: In the event of an application error, all safety outputs
switch to the OFF state. Once the cause of the error has been rectified, the safety
function must be restarted.
Reset required
Signals that a reset is possible. A connected lamp lights up if the restart interlock has
been triggered and the protective field is then clear again.
Monitoring result
Indicates the status of the active field. A connected lamp lights up if an object is
detected in the field.
Reset required (flashing)
Signals that a reset is possible. A connected lamp flashes if the restart interlock has
been triggered and the protective field is then clear again.
Further topics
•
"Status indicator with the display", page 155
7.13.2
Inputs
Signal of the machine controller for switching between monitoring cases.
7
CONFIGURATION
132
O P E R A T I N G I N S T R U C T I O N S | microScan3 Pro I/O
8025424/1ELL/2022-01-21 | SICK