Menu Structure
Speed
MF1 is used as speed switching output. Active when "Limit" is exceeded.
The switching hysteresis is fixed at ± 0.1 m/s.
Active
Inactive
Limit
Range
0.0 … 9.9 m/s
Speed > Limit
Speed < Limit
Sign
+/
–
Monitoring in both movement directions
+
Monitoring in movement direction "+"
(increasing distance)
–
Monitoring in movement direction "-"
(decreasing distance)
MF2
Parameterizable output
Active State
Parameterization of the switching logic
Active 1
HIGH-level at active output (closer/NO)
Active 0
LOW-level at active output (opener/NC)
Function
Distance
see 3.4.3
MF2 is used as distance switching output.
Service (default)
see 3.4.4
MF2 is used as service output.
Speed
see 3.4.3
MF2 is used as speed switching output.
Monitor
(for SSI or Hiperface version only): Displayed if monitor
interface is set to ON in 3.1.4 or 3.1.5.
Distance
MF2 is used as distance switching output.
Active when "UpperLimit" is exceeded.
Inactive when below "LowerLimit".