64
4. Parameter description
Parameter
<Setting>
•
The set value of P.37 is the mechanical speed of the inverter when its output frequency is 60Hz.
For example: if the transmitting belt speed is 950 m/minute when the inverter output frequency is
60Hz, P.37 shall be set to 950. In
‘
output frequency monitoring mode
’
, the screen will display the
speed of the transmitting belt.
Note: 1. There
’
s minute discrepancy between the displayed mechanical speed and the actual one.
2. Please refer to Section 3-2 for detailed operation of the
‘
operation panel working mode
’
.
3. When the output mechanical speed is more than 99998, the screen will display 99999.
4.18
Voltage signal selection and target frequency (P.38, P.73, P.139, P.140,
P.141)
P.38
“
The maximum output Frequency (the target frequency is set by the input
signal across terminal 2-5)
”
P.73
“
Voltage signal selection
”
P.139
“
Voltage signal bias
”
P.140
“
Voltage signal gain
”
P.141
“
Bias polarity
of voltage signal
and Reverse Motion of Negative Bias
”
Related parameters
P.80~P.84, P.86,P.126~P.128
“
Multi-function terminals selection
”
P.79
“
Operation mode selection
”
P.189
“
Default function
”