126
Appendix 1 Parameter list
Parameter list
Parameter
number
Name
Setting range
Minimum
setting
unit
Default value
User
setting
value
Refere
nce
page
P.0
Torque boost
0~30%
0.1%
(Note 1)
P46
120Hz
(
0kW~55kW
)
P.1
Maximum frequency
0~120Hz
0.01Hz
60Hz
(
75kW and above
)
P47
P.2
Minimum frequency
0~120Hz
0.01Hz
0Hz
P47
P.3
Base frequency
0~400Hz
0.01Hz
50Hz/60Hz
(Note 2)
P48
P.4
Speed 1 (high speed)
0~400Hz
0.01Hz
60Hz
P49
P.5
Speed 2 (middle speed)
0~400Hz
0.01Hz
30Hz
P49
P.6
Speed 3 (low speed)
0~400Hz
0.01Hz
10Hz
P49
P.7
Acceleration time
0~360.00s/
0~3600.0s
0.01s/0.1s
20.00s
P50
10s
(
0kW~7.5kW
)
P.8
Deceleration time
0~360.00s/
0~3600.0s
0.1s/0.01s
30s
(
11kW and above
)
P50
P.9
Electronic thermal relay
capacity
0~500A
0.01A
Motors rated current
(Note 1)
P51
P.10
DC
injection
brake
operation frequency
0~120Hz
0.01Hz
3Hz
P52
P.11
DC
injection
brake
operation time
0~60
s
0.1
s
0.5
s
P52
4%
(
0kW~7.5kW
)
2%
(
11kW~55kW
)
P.12
DC
injection
brake
voltage
0~30%
0.1%
1%
(
75kW and above
)
P52
P.13
Starting frequency
0~60Hz
0.01Hz
0.5Hz
P53
P.14
Load pattern selection
0~13
1
0
P54
P.15
JOG frequency
0~400Hz
0.01Hz
5Hz
P56
P.16
JOG
acceleration
/
deceleration time
0~360.00s/
0~3600.0s
0.1s/0.01s
5.00s
P56
P.17
Reserved
P.18
High-speed
maximum
frequency
120~400Hz
0.01Hz
120Hz
P47
P.19
Base frequency voltage
0~1000V, 99999
0.1V
99999
P48
P.20
Acceleration/deceleration
reference frequency
1~400Hz
0.01Hz
50Hz/60Hz
(Note 2)
P50
P.21
Acceleration/deceleration
time increments
0,1
1
0
P50
P.22
Stall prevention operation
level
0~200%
0.1%
150%
P57
PDF created with pdfFactory trial version