85
4. Parameter description
Parameter
4.32
Stop or Reset function selection (P.75
)
P.75
“
Stop or Reset function selection
”
Parameter
Factory setting
Setting range
Remarks
75
1
0, 1
---
<Setting>
•
When P.75=0, it is only suitable for PU mode and H2 mode (combined mode 2). Pressing
STOP
RESET
during
running is used to stop the motor.
•
When P.75=1, it is only suitable for the mode chosed. Pressing
STOP
RESET
during
running is used to stop
the motor.
•
Only at trouble state, we can press
STOP
RESET
for 1.0s to reset the inverter, and then the inverter will
show the power on state.
Note: 1. In normal or abnormal conditions, the reset can be executed by P.997.
2. There are two built-in program emulational thermally-accumulating relay, namely,
‘
electronic thermal
relay
’
and
‘
IGBT module thermal relay
’
. Once reset occurs, the values of the two relay for
‘
electronic
thermal relay
’
and
‘
IGBT module thermal relay
’
will be set to zero.
3. In any modes except External mode or H2 mode, when P.75=1, the motor can be stopped by pressing
STOP
RESET
,
then the inverter displays E0, and all the functions of the inverter are disabled. It can restart as follows:
(1). Terminate external STF/STR command (In programmed operation mode, there
’
s no need to terminate
the start signal. The inverter will continue to run at the section where it stopped after reset.)
(2). Press
.
At another mode, the inverter will normal operate nutil power on again.
4.33
Parameters write protection (P.77)
P.77
“
Parameters write protection
”
Parameter
Factory setting
Setting range
Remarks
77
0
0~2
---