4. Parameter description
Parameter
4.27
Zero current detection (P.62, P.63)
P.62
“
Zero current detection level
”
P.63
“
Zero current detection time
”
Parameter
Factory setting
Setting range
Remarks
62
5%
0~200%, 99999
99999: function invalid
63
0.5s
0.05~1s, 99999
99999: function invalid
<Setting>
•
Assume that the rated full-load current of the inverter is 20A, P.62=5% and P.63=0.5s, in this case
if the output current is lower than 2
0
×
5%=1A for more than 0.5s, a signal(OMD) is output, which
is depicted in the figure below.
•
If the set value of P.62 or P.63 is 99999, the zero current detection is disabled.
Note: In this paragraph OMD is one of the function names of
‘
multi-function output terminal
’
. Please refer to P.40
、
P.129
、
P.130 for function selection and features, and section 2-5 for wiring.
P.64
→
Please refer to P.54