4. Parameter description
Parameter
4.16
Communication function (P.32, P.33, P.36, P.48~P.53, P.153~P.154)
P.32
“
Serial communication Baud rate selection
”
P.33
“
Communication protocol selection
”
P.36
“
Inverter station number
”
P.48
“
Data length
”
P.49
“
STOP bit length
”
P.50
“
Parity check selection
”
P.51
“
CR, LF selection
”
P.52
“
Number of communication retries
”
P.53
“
Communication check time interval
”
P.153
“
Communication error handling
”
P.154
“
Modbus protocol selection
”
●
When the communication parameters are revised, please reset the inverter.
●
The SF-type inverters have two communication protocols to selection, Shihlin protocol and
Modbus protocol. If the communication expansion board is selected, the corresponding
communication protocol is provided. P.32, P.36, P.52, P.53, and P.153 are applied to both of the
protocols. P.48~P.51 is only applied to the Shihlin protocol
,
and P.154 is only applied to Modbus
protocol.
Parameter
Factory
setting
Setting range
Remarks
0
Baud rate: 4800bps
1
Baud rate: 9600bps
32
1
0~2
2
Baud rate: 19200bps
0
Modbus protocol
33
1
0, 1
1
Shihlin protocol
36
0
0~254
(Note 1)
0
Data length: 8 bit
48
0
0, 1
1
Data length: 7bit
0
STOP bit length: 1 bit
49
0
0~1
1
STOP bit length: 2 bit
0
Not Given
1
odd
50
0
0~2
2
even