72
4. Parameter description
Parameter
< Setting >
•
When P.120=0, if the set condition of P.40 (P.85, P.129, P.130) is met, the signal will be output
directly.
•
When P.120=0.1~3600, if the set condition of P.40 (P.85, P.129, P.130) is met, the signal will be
output after the set time.
For example: FU (Output frequency detection) function (For example: P.42/P.43=40Hz)
Note: 1. The multi-function output terminal is SO, SE. When P.40=1 (the default value), it means
‘
SU
’
. When
different value is set, the corresponding function will change as shown in the above table.
2. The internal electrical structures for the multi-function output terminals are
‘
open collector output
’
.
Please refer to Section 2-5-2 and Section 2-5-3 for wiring.
3. When the set value of P.85 is 5(the default value), the function of the multi-function relay ABC is
ALARM. When the value of P.85 is revised, its function changes respectively as the corresponding
function list in the table above.
4.21
Up-to-frequency sensitivity (P.41)
P.41
“
Up-to-frequency sensitivity
”
Parameter
Factory setting
Setting range
Remarks
41
10%
0~100%
---
<Setting>
•
If P.41=5%, a signal (SU) is output when the output frequency enter the
‘
5% region near the target
frequency
’
. For example: the target frequency is set to 60Hz, and P.41=5%, then if the output
frequency is between 60
±
60
×
5%=63Hz and 57Hz region, the SU signal is output.