133
UK
2.3 Indication of the next maintenance procedure
2.2 Setting the time delay
Allows optimised pumping times as a function of the total dynamic head
Gives the date of the next maintenance procedure, a reminder on the screen will be displayed on
the scheduled date. Maintenance frequencies are different depending on the area of use of the station
(according to EN12056-4).
For:
• Industrial use: 3 months • Small collective use: 6 months
• Domestic use: 12 months
Press OK to confirm the type of use.
In order to empty the tank as much as possible and optimise the pumping of the materials on the surface,
we can increase the engine shut-down time. Pre-set to 4 seconds after float OFF. The higher the pump,
the longer the time delay will be.
The motor activation time is pre-set to 30 seconds. After thirty seconds of continuous operation, the
second motor is activated to reinforce the first one. If this parameter is too long (for the client), it is possible
to decrease the delay.
10:48:50
AC
Industriel:
Maintenance :
Next: FEVRIER 2017
Petit collectif:
Domestique:
OK
P1
P2
➤
➤
➤
➤
10:47:10
AC
JOURNAL
Liste Alarme
Temps pompes
Graph U
Graph I1
Graph I2
››
› ›
3. Consulting the log
Enter the
history
3.1 List of alarms
Alarm indicator in real time, with identification of the problem detected for
quick maintenance. Option to view alarm history.
10:47:18
AC
ALARM 16
ALM:Pas de AC
Le 29 DECEMBRE 2016
a 10:52:32
ALM17
➞
ALM15
➞
Indication of the
type of alarm
Date and time
of last alarm
History check
10:48:42
AC
4s
PUMP DELAY:
Delay to activate P2
30s
OK
1. Choice of languages
2. Setting parameters
Allows certain parameters to modified to optimise the operation of the pumping station.
2.1 Setting the date and time
Parameter required for alarm management, history and maintenance
periods. The date and time will be saved as soon as they are validated
with OK.
Up and down arrow to
increase or decrease
Left and right arrow
to change from day to
month, to year, to hour,
to minute ... until OK
which will validate the
entry.
LANGUE
››
P1
P2
10:46:52
AC
➤
➤
➤
➤
10:45:53
AC
LANGUE
FRANCAIS
ENGLISH
ESPAGNOL
DEUTSCH
››
› ›
Press to select
language
Return
Switch to next menu,
language selection
REGLAGES
› ›
10:48:20
AC
P1
P2
10:48:30
AC
➤
➤
➤
➤
Date :
29
DECEMBRE 2016
Il est : 10:48 et 30s
OK
Содержание SANIFOS 110
Страница 2: ...2 FR ...
Страница 3: ...3 FR p 4 p 31 p 58 p 85 p 112 p 139 p 166 FR UK IT PT DE ES NL ...
Страница 16: ...16 FR Flotteurs SANIFOS 500 Rassembler les câbles flotteurs Les fixer à la barre inox à l aide d un tyrap ...
Страница 70: ...70 IT Galleggianti SANIFOS 500 Riunire i cavi galleggianti Fissarli alla barra inox usando un tyrap ...
Страница 124: ...124 UK SANIFOS 500 floats Gather together the float cables Fix them to the stainless steel bar using a tie wrap ...
Страница 151: ...151 ES Flotadores SANIFOS 500 Juntar los cables flotadores Fijarlos a la barra inoxidable con ayuda de una brida ...
Страница 178: ...178 PT Flutuadores SANIFOS 500 Juntar os cabos flutuadores Fixá los na barra inoxidável com a ajuda de um tyrap ...