52
Operating Instructions – MOVITRAC® LTP
9
MODBUS Control
Software
153
Analog output function
0 ... 10
–
–
Digital output ctrl. limit (h)
0 ... 100
Located in lower byte
–
154
Digital output ctrl. limit (L)
0 ... high limit
Located in higher byte
–
155
Relay output function
0 ... 6
–
–
Relay control limit (h)
0 ... 100
Located in lower byte
–
156
Relay control limit (L)
0 ... high limit
Located in higher byte
–
157
Relay output mode
0 ... 1
0: Normally open
1: Normally closed
–
158
Zero speed holding time
0 ... 60 s
1 decimal place
600 = 60.0 s
159
Start mode select
0 ... 6
0: Edgr-r
1: Auto_0
2 ... 6: Auto_1 ... Auto_5
–
160
Reserved
0
Read as zero
–
161
Keypad restart mode
0 ... 3
–
–
162
Enable standby
0 ... 60
Data unit in seconds (s)
–
163
Display scaling factor
0 ... 30000
3 decimal places
300 = 0.3.00
164
Display scaling source
0 ... 1
0: 2nd analog input
1: Drive speed
–
165
Brake circuit enable
0 ... 3
–
–
166
Effective switching freq.
0 ... 4
(drive dependent)
0: 4 KHz
1: 8 KHz
2: 16 KHz
3: 24 KHz
4: 32 KHz
–
167
2nd dec. ramp time (s)
0 ... 30000
1 decimal place
300 = 30.0 s
168
MODBUS baudrate
0 ... 4
0: 9600 bps
1: 19200 bps
2: 38400 bps
3: 57600 bps
4: 115200 bps
169
Drive comms address
1 ... 63
–
–
170
Master / Slave mode
0 ... 1
Only for Optibus, not MODBUS
–
171
Speed scaling factor
0 ... 5000
1 decimal place
300 = 30.0 %
172
Bipolar analog input format
0 ... 2
0: 0 ... 24 V
1: 0 ... 10 V
2: –10 ... 10 V
–
173
Bipolar analog input scaling
0 ... 5000
1 decimal place
300 = 30.0 %
174
Bipolar analog input offset
–5000 ... 5000
1 decimal place
300 = 30.0 %
175
2nd analog input format
0 ... 3
0: 0 / 24 V digital
1: 0 ... 10 V
2: 4 ... 20 mA
3: 0 ... 20 mA
–
176
2nd analog input scaling
0 ... 5000
1 decimal place
300 = 30.0 %
177
Digital speed reference scaling
control
0 ... 3
–
–
178
Analog output format
0 or 3
0: 0 ... 10 V
1: 4 ... 20 mA
2: 10 ... 0 V
3: 20 ... 4 mA
–
179
Extended access code
0 ... 999
–
–
180
Parameter lock
0 or 1
0: Unlock
1: Locked
–
181
Drive run time
Read only
Read values as hours
–
182
Drive power rating
Read only
Power stated to 2 decimal places
–
183 ...
198
Reserved
Read only
Read as zero
–
Adr
Description
Data range
Data format
Example