Operating Instructions – MOVITRAC® LTP
49
9
MODBUS Control
Software
9
Software
9.1
MODBUS Control
9.1.1
Specification
The following table highlights the specification for the MODBUS RTU implementation in
MOVITRAC
®
LTP.
9.1.2
Memory map
Protocol
MODBUS RTU
Error check
CRC
Baud rate
9600 bps, 19200 bps, 38400 bps, 57600 bps, 115200 bps (default)
Data format
1 start bit, 8 data bits, 1 stop bit, no parity
Physical signal
RS-485 (2-wire)
User interface
RJ11
Register
Upper byte
Lower byte
Command
Type
1
Command
–
03,06
Read / Write
2
Speed reference
–
03,06
Read / Write
3
Torque reference
–
03,06
Read / Write
4
Acceleration ramp time
Deceleration ramp time
03,06
Read / Write
5
Reserved
–
03
Read only
6
Error code
Drive status
03
Read only
7
Motor speed
–
03
Read only
8
Motor current
–
03
Read only
9
Motor torque
–
03
Read only
10
Motor power
–
03
Read only
11
Digital input status
–
03
Read only