Operating Instructions – MOVITRAC® LTP
29
6
Easy startup
Startup
6.2.2
Keypad mode
To operate in keypad mode:
• Change P1-12 to 1 (uni-directional) or 2 (bi-directional).
• Place a wire link or switch between terminals 1 and 2 on the user terminal block to
enable the drive.
• Now press the <start> key. The drive enables at 0.0 Hz.
• Press the <up> key to increase speed.
• To stop the drive, press the <stop> key.
• If the <start> key is now pressed, the drive will return to its original speed, unless con-
figured to start from zero speed (see P2-19). (If bi-directional mode is enabled
(P1-12 = 2), pressing the <start> key reverses the direction).
6.2.3
Key parameters
• Adjust the maximum and minimum speed limit using P1-01 and P1-02.
• Adjust the acceleration and deceleration times using P1-03 and P1-04.
• Set up the motor nameplate data in parameters P1-07 to P1-10.
NOTE
The desired target speed can be preset by pressing the <stop> key whilst the drive is
stopped. When the <start> key is subsequently pressed, the drive will then ramp to this
speed.