Operating Instructions – MOVITRAC® LTP
8
Parameter specifications:
Parameters
Par.
Description
Range
Default
Explanation
P2-14(h)
User relay output control
high limit
Speed : 0 ... 200 %
(200 % = max speed)
Torque : 0 ... 200 %
(200 % = rated torque)
PID feedback : 0 ... 200 %
(200 % = max 2nd analog input)
100 %
User relay output closes (P2-15=0) when
selected value in P2-13 larger than this
limit.
Limit in P2-14 relates to speed if P2-13 = 4,
to motor torque if P2-13 = 5 or to the PID
feedback value (2nd analog input) if
P2-13 = 6.
P2-14(L)
User relay output control
low limit
0 … P2-14(h)
100 %
Digital output state back to logic 0 when
selected value in P2-13 less than or equal
to this limit. (P2-13 = 4,5 or 6)
P2-15
Relay output mode
0:
Normally Open (NO)
0 (NO)
The drive must be powered up for the relay
contacts to be closed.
1:
Normally Closed (NC)
P2-16
Zero Speed holding time
0 …
60 s
0.2 s
Determines the time for which the zero
speed is held on the output before disabling
the drive.
P2-17
Start mode select
Edgr-r
Close digital input 1 after
power up to start drive
Auto-0
When set to Edge-r, if drive is powered up
with digital Input 1 closed (enabled), drive
will not run.
The switch (digital input 1) must be opened
and closed after power up or after a clear-
ing a trip for the drive to run.
When set to Auto-0, drive will run whenever
digital input 1 is closed (if not tripped).
Auto-1…5 makes 1…5 attempts to auto-
matically restart after a trip (20 s between
attempts in default).
Drive must be powered down to reset the
counter.
Auto-0
Drive runs whenever digi-
tal input 1 is closed
Auto-
1…5
As Auto-0, except 1..5
attempts to restart after a
trip
P2-18
Spin Start Enable
(V/f mode only)
0:
Disable
0
When enabled, drive detects motor speed
and starts driving the motor from this speed
(the motor speed can be in both directions:
forward or reverse).
A short delay of approx. 1 s will result after
enabling the drive before speed is
detected.
This function only works when parameter
P4-01 = 2.
1:
Enable
P2-19
Keypad restart mode
0:
Minimum speed
1
If set to 0 or 2, drive will always start from
minimum speed.
If set to 1 or 3, drive ramps up to the oper-
ating speed prior to the last STOP com-
mand.
If set to 2 and 3, the status of digital input 1
controls drive to start or stop. The start and
stop button will not work in this case.
1:
Previous speed
2:
Min-speed (Auto-r)
3:
Previous speed (Auto-r)
P2-20
Standby mode
0: Disable
1 … 60 s
0.0 s
If P2-20 > 0, drive enters standby mode
(disables output) if minimum speed is main-
tained for the time specified in P2-20.
If P2-16 > 0, this function is disabled.
P2-21
Display scaling factor
0.000 ... 30.000
0.000
Disabled if set to zero.
The variable selected in P2-22 is multiplied
by this factor and displayed as a real-time
value on the drive, in addition to speed, cur-
rent and power.
P2-22
Display scaling source
0:
2nd analog input
0
Selects the variable to be scaled by the fac-
tor set in P2-21.
1:
Motor speed
2:
Motor torque
3:
Motor current
P6..
P60.
P600