Operating Instructions – MOVITRAC® LTP
8
Selection of Parameter P2-01, Digital Input Function
Parameters
10
O: Stop (Disable)
C: Run Forward
O: Stop (Disable)
C: Run Reverse
External trip input:
O: Trip
C: OK
Bipolar analog
input
Connect an external
PTC motor thermistor
or similar to DI3
11
O: Stop (Disable)
C: Run (Enable)
O: Analog input
C: Preset speed 1
External trip input:
O: Trip
C: OK
Bipolar analog
input
Connect an external
PTC motor thermistor
or similar to DI3
12
O: Stop (Disable)
C: Run (Enable)
O: Preset speed 1
C: Analog input
External trip input:
O: Trip
C: OK
Bipolar analog
input
Connect an external
PTC motor thermistor
or similar to DI3
13
Normally Open (NO)
Momentarily close to run
forward
Normally Closed
(NC)
Momentarily open to
run
O: Analog input
C: Preset speed 1
Bipolar analog
input
–
14
Normally Open (NO)
Momentarily close to run
forward
Normally Closed
(NC)
Momentarily open to
stop
Normally Open (NO)
Momentarily close to
run reverse
Bipolar analog
input
–
15
O: Stop (Disable)
C: Run (Enable)
O: Forward
C: Reverse
O: Decel ramp 1
C: Decel ramp 2
Bipolar analog
input
–
16
O: Stop (Disable)
C: Run (Enable)
O: Forward
C: Reverse
O: Decel ramp 1
C: Decel ramp 2
O: Preset speed 1
C: Preset speed 2
–
17
Normally Open (NO)
Momentarily close to run
forward
Normally Closed
(NC)
Momentarily open to
stop
Normally Open (NO)
Momentarily close to
run reverse
O: Preset speed 1
C: Keypad mode
Up and Down buttons
can be used to set the
speed when analog
input is set to keypad
mode.
18
O: Stop (Disable)
C: Run (Enable)
Open
Open
O: Terminal mode
C: Keypad mode
Preset speed 1
Closed
Open
Preset speed 2
Open
Closed
Preset speed 3
Closed
Closed
Preset speed 4
19
O: Stop (Disable)
C: Run (Enable)
O: Analog input
C: 2nd analog input
2nd analog input
Bipolar analog
input
–
20
O: Stop (Disable)
C: Run (Enable)
2nd digital output
(+24 V)
O: Analog input
C: Preset speed 1
Bipolar analog
input
2nd digital output
shows drive healthy
21
O: Stop (Disable)
C: Run (Enable)
2nd digital output
(+24 V)
O: Forward
C: Reverse
Bipolar analog
input
2nd digital output
shows drive healthy
22
O: Stop (Disable)
C: Run (Enable)
2nd digital output
(+24 V)
External trip input:
O: Trip
C: OK
Bipolar analog
input
2nd digital output
shows drive healthy
P2-01
Digi input 1 (DI1)
Digi input 2 (DI2)
Digi input 3 (DI3)
Analog input (AI)
Comments / Preset
value
NOTE
When P2-01 = 20, the 2nd digital input is configured as an output, which o24 V
when the drive is healthy. If the drive is not healthy, the output will be 0 V.
When connecting a motor thermistor, connect it between terminals 1 and 4.
Set P2-01 to 6, 10, 11, 12 or 22 (uses external trip input).
P6..