Operating Instructions – MOVITRAC® LTP
55
10
Conformance
Technical data
10
Technical data
10.1 Conformance
All products conform to the following international standards:
• UL 508C Power conversion equipment
• EN 61000-6 / -2, -3, -4 Generic immunity / Emission standards (EMC)
• Enclosure protection level according to NEMA 250, EN 60529
• Flammability rating according to UL 94
• cUL Power conversion equipment, certified for Canada
10.2 Environmental
Operational ambient temperature range
0 ... 50 °C at default PWM frequency (IP20)
0 ... 40 °C at default PWM frequency (IP55, NEMA 12k)
Maximum ambient temperature derating
4 % / °C up to 55 °C for IP20 drives
4 % / °C up to 45 °C for IP55 drives
Storage ambient temperature range
–40 ... +60 °C
Maximum altitude for rated operation
1000 m
Derating above 1000 m
1 % / 100 m to max. 2000 m
Maximum relative humidity
95 % (non-condensing)
Protection rating cabinet drive
IP20
Protection rating high enclosure drive
IP55, NEMA 12 k
P