Operating Instructions – MOVITRAC® LTP
7
Fault codes and history
Operation and Service
7.2.3
Fault codes
Trip message
Explanation
Solution
"P-dEF"
Factory default parameters have
been loaded.
Press STOP key. Drive is ready to configure for
required application.
“O-I”
Over-current on drive output to
motor.
Excess load on motor.
Over temperature on drive heat-
sink.
•
Check motor and motor connection cable for
ph-ph or ph-Earth short circuit
•
Check load mechanically for a jam or stalled
condition or shock loads.
•
Ensure motor nameplate parameters are
entered correctly, P1-07, P1-08, P1-09.
•
If operating in Vector mode (P4-01 = 0 or 1):
•
also check motor power factor in P4-05.
•
reduce speed loop gain in P4-03.
•
Ensure an autotune has been successfully
completed for the connected motor.
•
Increase the ramp-up time in P1-03.
“I_t-trP”
Drive overload trip, occurring
when the drive has been deliver-
ing > 100 % rated current (set in
P1-08
) for a period of time. The
display flashes to indicate an
overload condition.
•
Increase acceleration ramp or decrease motor
load.
•
Check cable length is within drive specification.
•
Ensure motor nameplate parameters are
entered correctly, P1-07, P1-08, P1-09.
•
If operating in Vector mode (P4-01 = 0 or 1),
also check motor power factor in P4-05.
•
Ensure an autotune has been successfully
completed for the connected motor.
•
Check the load mechanically to ensure it is free
and no jams, blockages or other mechanical
faults exist.
"OI-b"
Brake channel over current. Over
current in the brake resistor cir-
cuit.
•
Check the cabling to the braking resistor.
•
Check the braking resistor value.
•
Ensure minimum resistance values from the
rating tables are observed.
"OL-br"
Braking resistor overload
•
Increase deceleration time, reduce load inertia
or add further braking resistors in parallel.
•
Ensure minimum resistance values from the
rating tables are observed.
“PS-trP”
Internal power stage fault
Trip on drive enable:
•
Check for wiring error or short circuit.
•
Look for ph-ph or ph-Earth short circuit.
Trip during operation:
•
Check for sudden overload or over-tempera-
ture.
•
Additional space or cooling may be required.
“O_Uolt”
Over-voltage on DC bus
•
Check supply voltage is within limits.
•
If trip occurs on deceleration, increase deceler-
ation time in P1-04.
“U_Uolt”
Under-voltage on DC bus
Occurs routinely when drive powered down. If it
occurs whilst running, check supply voltage.
“O-t”
Heatsink over temperature
•
Check drive cooling and enclosure dimensions.
•
Additional space or cooling may be required.
“U-t”
Under temperature
•
Occurs when ambient temperature is less than
–10 °C
•
Raise temperature to over –10 °C in order to
start the drive.
"th-Flt"
Faulty thermistor on heatsink
Contact SEW-EURODRIVE Service.
“E-triP”
External trip (connected to digital
input 3)
•
E-trip on digital input 3. Normally closed contact
has opened for some reason.
•
Check motor thermistor (if connected).
"4-20 F"
Analog input current out of range
•
X3
–
Check input current is within range defined
in P2-36.
–
Check cable connection.
0
0
I