Operating Instructions – MOVITRAC® LTP
39
8
Parameter specifications:
Parameters
P2-23
Brake circuit enable
0:
Disable
0
Enables the internal brake chopper.
Overload protection in software when set to
1 or 2. See rating tables for resistor sizing
guidelines.
1:
lo power
2:
hi power
3:
Enable, no protection
P2-24
Effective switching
frequency
S1, S2 230 V, 4 ... 32 kHz
16 kHz
Effective power stage switching frequency.
X1: higher switching frequency means less
noise development on the motor but higher
losses at output stage.
S2
400 V, 4 ... 32 kHz
8 kHz
S3, S4 400 V, 4 ... 24 kHz
4 kHz
S5, S6 400 V, 4 ... 16 kHz
4 kHz
Auto
"Auto" selects minimum possible switching
frequency for the speed range selected to
minimize losses in spindle applications.
(P2-24 must be 16 x P1-01 or greater.)
P2-25
Second deceleration ramp
time
0 s … 3000 s
0.0 s
Selected automatically on mains loss if
P1-05 = 2. Can also be selected via digital
inputs during operation.
P2-26
MODBUS communication
baudrate
t9.6, t19.2, t38.4, t57.6, t115.2
r9.6, r19.2, r38.4, r57.6, r115.2
0 Kbaud
MODBUS RTU serial data link communica-
tion baudrate.
A ’t’ suffix indicates the drive will trip if com-
munication with the network master is lost,
after the time period set in P6-08.
An ’r’ suffix indicates that the drive will
ramp to stop if communication with the net-
work master is lost, after the time period set
in P6-08.
P2-27
Drive communication
address
0:
Disable
1
Distinct drive address used for all drive
serial communications.
1 ...
63:
Communication address
P2-28
Master / Slave mode select 0:
Slave mode
0
When in Master mode, the drive transmits
its operational status via the serial data link.
Used to control slave drives via the serial
link. P2-27 must be 1 for Master mode.
1:
Master mode
P2-29
Digital speed reference
preset scaling factor
0 … 500 %, steps of 0.1 %
100.0 %
The digital speed reference input to the
drive is scaled by this factor when
P2-35 = 1. Operates on references origi-
nating from the serial data link. Can be
used as an electronic gearbox for Master /
Slave applications.
P2-30
Bipolar analog input format
0 ... 24 V
0 ... 10 V
–10 ... 10 V
–24 ... 24 V
0 ... 24 V
Configures the analog input format to
match the reference signal connected to
terminal 6. Only voltage signals can be
directly connected, mA reference signals
require an external resistor connection.
P2-31
Bipolar analog input scal-
ing
0 ... 500 %
100.0 %
Scales the analog input by this factor.
Set to 200 % to give full speed range con-
trol with 0 ... 5 V input
(when P2-30 = 0 ... 10 V).
P2-32
Bipolar analog input offset
–500 % ... +500 %
0.0 %
Sets the offset from zero at which speed
starts to ramp up.
Value is “%” of the full scale input voltage.
P2-33
2nd analog input format
0 / 24 V (digital input)
0 ... 10 V,
4..20 mA, 0 ... 20 mA
0 / 24 V
Determines the format of the 2nd analog
input.Selecting 0 / 24 V sets up the input as
a digital input.
P2-34
2nd analog input scaling
0 ... 500 %
100.0 %
Scales the 2nd analog input by the factor
set in this parameter.
Par.
Description
Range
Default
Explanation
P6..
P60.
P600