Operating manual 810378-BAL-EN-170330
Mach/30 2017
Page 37 of 54
1
0
Warning: invalid target value for
voltage or current
1: An invalid parameter (value out-
side of range) has been received
0: Parameter valid
1..7
Reserve
2
0
Missing DRIVE power (when HV
on)
1: 24 V DRIVE is not on and HV ON
has been set
0: No error or error acknowledged
1
Reserve
2
U
min
switch off
1: Umin switch off
0: No error or error acknowledged
3
I
max
switch off
1: Imax switch off
0: No error or error acknowledged
4
Electrical arc switch off
1: Electrical arc detected and
switched off
0: No error or error acknowledged
5
Power loss too high
1: Output power too low in relation-
ship to the input power
0: No error or error acknowledged
6
Over-voltage switch off
1: An actual value above 109 kV has
been detected
0: No error or error acknowledged
7
Node guarding error switch off
1: Switch off after loss of node guard-
ing signal
0: No error or error acknowledged
3
0
Warning invalid parameters
1: An invalid parameter (value out-
side of range) has been received in
the object directory
0: Parameter valid
1
HV ON specification during relay
test
1: HV ON was set during activated
relay test (HV remains off)
0: No error or error acknowledged
2
Reserve
3
Self-test
1: Self-test of the smart-E malfunc-
tion (program check sum, internal
hardware, current measurement*)
0: No error or error acknowledged
4..7
Reserve
* The check of the current measurement occurs when switching on the device (24 V
CPU on), also for each high voltage switch off.