3.1. Service life
The service life is set to a maximum of
20 years
, since this value is based on the
methods in EN 13849. In addition, Performance Level d does not apply to residual en-
ergy monitoring.
Obvious defective devices must be shut down immediately.
3.2. Further requirements for the surrounding system
The HV generator must only be used in electrostatic systems within a
temperature range
of 15 °C to 40 °C
and with a relative humidity be-
tween
10 % and 70 %
(not condensing).
The HV generator is intended for
operation in a specific stationary
system in an industrial
. Due to the occurring conductive or radiated
interferences, difficulties can possibly arrive in ensuring the electromag-
netic compatibility in other environments.
To prevent hazards the entire system must undergo a risk analysis. Es-
pecially the Performance Level required in the above mentioned product
standards for safety functions can only be met via a safety concept of the
entire system.*
* Since the sprayer system is connected to the high-voltage generator via a high-
voltage cable, a specific Performance Level by this unit can only be ensured up to the
connection point of the HV cable. The cable to the sprayer system must be consid-
ered separately.