Operating manual 810378-BAL-EN-170330
Mach/30 2017
Page 38 of 54
PROFINET interface specifications
9.
(smart-E 310p, smart-E510p, smart-E 310Dp, smart-E 510Dp)
9.1. Bus interface
Profinet based on the ethernet physical layer. To create communication between the
smart-E 310 or smart-E 510 and profinet controller (PN controller), no special steps are
required. The IP address is set automatically. See the manual of your PN controller for
further information.
For examples of setting up communications, see our smart-E
website
www.smart-E310.de
.
9.2. Application interface
9.2.1.
GSD-Files
Use our standardized "GSD" files to load the applications interface
to your control software.
GSD files are simple text files that use network configuration tools
to support the identification of products and their simple direction in
a network.
SCHNIER provides a GSD file with all parameters and format in-
formation of the HV generator. It can be obtained on the smart-E
website
www.smart-E310.de
.
9.2.2.
Write the data sets (record writes)
The user interface uses datasets (records) for two parameter settings of the HV gener-
ator:
Byte
Parameters
Unit
Min
Stand-
ard
max
Remarks
0
kV ramp
kV/s
1
20
100
Speed when starting up
voltage
1
Sensitivity of
electrical arc
detection
-
0
5
10
0: Electrical arc detection
off
1~10: Highest to lowest
sensitivity.
As usual this parameter could be unchanged.
Do not switch off electrical arc detection in normal operation!
2..15
Reserve