Communication functions
Important notes on the weekly and calendar switching programs:
All the registers for unused switching commands should contain the value 0.
•
The switching commands should be entered in the chronological order of
•
time/date. The fi rst command of a day/year should, therefore, be under
‚Command1‘.
Modbus data points (coils)
6.3.2
Coil no.
Description
Comment
Can be
set?
Can be
deleted?
0
1
4
Collective level bit
Controller controls all functions inde-
pendently of the control station
Yes
No
BMS
AUTONO-
MOUS
32
Binary input, Cl. 22
Binary input, Cl. 22/Cl. 21
No
No
OPEN
CLOSED
57
Binary output term. 6
Relay output terminal 6 = UP
(->CL96)
Yes
Yes
OPEN
CLOSED
60
Binary output term. 7
Relay output terminal 7 (->CL99)
Yes
Yes
OPEN
CLOSED
64
Binary output term. 8
Relay output terminal 8 (->CL100)
Yes
Yes
OPEN
CLOSED
61
Binary output term.
10
Relay output terminal 10 (->CL97)
Yes
Yes
OPEN
CLOSED
88
EBN AF1
Controller measures outdoor tempe-
rature (HR40010) itself
Yes
No
BMS
AUTONO-
MOUS
89
EBN BetrArt Rk1
Controller switches operating mode
Rk1 (HR40106) itself
Yes
No
GLT
AUTONO-
MOUS
90
EBN Stellsig Rk1
Controller controls actuation signal
Rk1 (HR40107) itself
Yes
No
GLT
AUTONO-
MOUS
91
EBN BetrArt Rk2
Controller switches operating mode
Rk2 (HR40108) itself
Yes
No
GLT
AUTONO-
MOUS
92
EBN Stellsig Rk2
Controller controls actuation signal
Rk2 (HR40109) itself
Yes
No
GLT
AUTONO-
MOUS
96
EBN Binary term. 6
Controller switches heating medium
pump UP1 (CL57) itself
Yes
No
BMS
AUTONO-
MOUS
97
EBN Binary term. 10
Controller switches term. 10 (CL61)
itself
Yes
No
BMS
AUTONO-
MOUS
99
EBN Binary term. 7
Controller switches term. 7 (CL60)
itself
Yes
No
BMS
AUTONO-
MOUS
100
EBN Binary term. 8
Controller switches term. 8 (CL64)
itself
Yes
No
BMS
AUTONO-
MOUS
116
EBN VorlSoll Rk1
Controller determines fl ow setpoint for
Rk1 (HR41000) itself
Yes
No
GLT
AUTONO-
MOUS
118
EBN VorlSoll Rk2
Controller determines fl ow setpoint for
Rk2 (HR41200) itself
Yes
No
GLT
AUTONO-
MOUS
150
DisableManual
Release manual levels
Yes
Yes
INACTIVE
AKTIV
157
DisableModem
Disable dialling to BMS
Yes
Yes
INACTIVE
AKTIV
158
Dial going
BMS dialling also with faults present
Yes
Yes
INACTIVE
AKTIV
159
Timeout BMS
BMS monitoring
Yes
Yes
INACTIVE
AKTIV
Modbus-Datenpunkte
Tab.8
When a function of the controller is specifi ed via Modbus (e.g. status of the UP
output), the associated level bit (as it is called, designated as EBN) is deleted on
the controller. The controller no longer controls the respective function itself in this
case. When Modbus communication has fi nished (e.g. modem link disconnected),
Level bits
Содержание equitherm EQJW245
Страница 2: ...2 127 www sauter controls com EQJW245 ...
Страница 6: ...6 127 www sauter controls com EQJW245 Content Table of figures 121 List of tables 123 Index 125 ...
Страница 8: ...8 127 www sauter controls com EQJW245 ...
Страница 10: ...10 127 www sauter controls com EQJW245 ...
Страница 12: ...12 127 www sauter controls com EQJW245 ...
Страница 54: ...54 127 www sauter controls com EQJW245 ...
Страница 78: ...78 127 www sauter controls com EQJW245 ...
Страница 88: ...88 127 www sauter controls com EQJW245 ...
Страница 92: ...92 127 www sauter controls com EQJW245 ...
Страница 102: ...102 127 www sauter controls com EQJW245 ...
Страница 104: ...104 127 www sauter controls com EQJW245 ...
Страница 106: ...106 127 www sauter controls com EQJW245 ...
Страница 108: ...108 127 www sauter controls com EQJW245 ...
Страница 110: ...110 127 www sauter controls com EQJW245 ...
Страница 112: ...112 127 www sauter controls com EQJW245 ...
Страница 122: ...122 127 www sauter controls com EQJW245 ...
Страница 124: ...124 127 www sauter controls com EQJW245 ...