EQJW245
25/127
www.sauter-controls.com
Commissioning
Parameter
Description
Range
Step
value
SP07 0
Infl uence of binary / pulse input (terminal 21, 22)
0 = No infl uence on HK1
1 = HK1 in back-up mode if contact closed
2 = HK1 in reduced mode if contact closed
3 = HK1 in nominal mode if contact closed
4 = Pulse input for quantity metering
5 = Seepage limitation
6 = Input for fault signal
0 to 6
1
SP08 0
Room sensor HK1 and 2nd fl ow sensor BW
0 = No room temperature recording
1 = Room sensor NI1000
2 = EGS52/15 or EGT333 with room sensor
3 = EGS52/15 or EGT333 without room sensor
4 = 2nd fl ow sensor for domestic water
0 to 4
1
SP09
0
Room temperature input for HK1
0 = not active
1 = active if T
Ri
> T
Rs
2 = active if T
Ri
< T
Rs
3 = active if T
Ri
<> T
Rs
0 to 3
1
SP10
20
Room temperature input scanning time HK1/[min]
1 to 100
1
SP11
0
Correct room temperature of HK! In K
-6.0 to +6.0
0.1
SP12
0
Outside temperature correction in K
-10.0 to +10.0
1
SP13
0
Return temperature recording T
RF1
0 = Return temperature not being recorded
1 = T
RF
is recorded up to max. return temperature limit
2 = T
RF
for maintaining return temperature
0 to 2
1
SP14
0
T
RF1
correction in K
-10.0 to +10.0
1
SP15
40
Proportional band PI – actuator 1 control in K
2 to 1000
1
SP16
240
Reset time PI – actuator 1 control in seconds
5 to 1000
1
SP17
120
Actuator 1 run-time in seconds
30 to 960
15
SP18
5
Minimum T
F
limit for heating 1 in °C
5 to 100
1
SP19
75
Maximum T
F
limit for heating 1 in °C
20 to 150
1
SP20
90
Upper limit (min. or max.) of T
RF
for HK1, 2 in °C
0 to 150
1
SP21
90
Lower limit (min. or max.) of T
RF
for HK1, 2 in °C
0 to 150
1
SP22
0
TA at which scheduled part of limiting function of T
RF
for HK1, 2 used
in °C
-49 to +49
1
SP23
1.0
Slope of limiting function of T
RF
for HK1, 2 in K/K
0 to 5
0.1
SP24
90
Return temperature limit during domestic water charging in °C
5 to 150
1
SP25
5
Intervention level in control of fi nal control element 1 if limit for T
RF1
[K/K] exceeded
0.1 to 10
0.1
SP26
no
Limit in pulses/min for max. fl ow rate and output
if at least one heating circuit and domestic water preparation is
active
no, 0.1 to 16;
60to 16000
0.1/1/10
SP27
no
Limit in pulses/min for max. fl ow rate and output if at least one hea-
ting circuit but not domestic water preparation is active
no, 0.1 to 16;
60 to 16000
0.1/1/10
SP28
no
Limit in pulses/min for max. fl ow rate and output if only domestic
water preparation is active, but none of the heating circuits
no, 0.1 to 16;
60 to 16000
0.1/1/10
SP29
0.0
Intervention level on T
F1
in K/min if fl ow rate/output limit exceeded
0.0 to 30.0
0.1
SP30
no
Limit in pulses/min for min. fl ow rate and output
no, 0.1 to 16;
60 to 16000
0.1/1/10
SP31
1
Domestic water functions
0 = no domestic water preparation
1 = BW preparation with 1 sensor
2 = BW preparation with 2 sensors
3 = BW preparation using fl ow control
0 to 3
1
Содержание equitherm EQJW245
Страница 2: ...2 127 www sauter controls com EQJW245 ...
Страница 6: ...6 127 www sauter controls com EQJW245 Content Table of figures 121 List of tables 123 Index 125 ...
Страница 8: ...8 127 www sauter controls com EQJW245 ...
Страница 10: ...10 127 www sauter controls com EQJW245 ...
Страница 12: ...12 127 www sauter controls com EQJW245 ...
Страница 54: ...54 127 www sauter controls com EQJW245 ...
Страница 78: ...78 127 www sauter controls com EQJW245 ...
Страница 88: ...88 127 www sauter controls com EQJW245 ...
Страница 92: ...92 127 www sauter controls com EQJW245 ...
Страница 102: ...102 127 www sauter controls com EQJW245 ...
Страница 104: ...104 127 www sauter controls com EQJW245 ...
Страница 106: ...106 127 www sauter controls com EQJW245 ...
Страница 108: ...108 127 www sauter controls com EQJW245 ...
Страница 110: ...110 127 www sauter controls com EQJW245 ...
Страница 112: ...112 127 www sauter controls com EQJW245 ...
Страница 122: ...122 127 www sauter controls com EQJW245 ...
Страница 124: ...124 127 www sauter controls com EQJW245 ...