EQJW245
27/127
www.sauter-controls.com
Commissioning
Parameter
Description
Range
Step
value
SP201
0
Effect of binary input on heating 2
0 = No infl uence
1 = HK2 in back-up mode if contact closed
2 = HK2 in reduced mode if contact closed
3 = HK2 in nominal mode if contact closed
4 = Pulse input for quantity metering
5 = Seepage limitation
0 to 3
1
SP202 0
HK2 room sensor
0 = No room temperature recording
1 = Room sensor NI1000
2 = EGS52/15 or EGT333 with room sensor
3 = EGS52/15 or EGT333 without room sensor
Remark: function only active if value SP31 <> 2
0 to 4
1
SP203
0
Room temperature input for HK2
0 = not active
1 = active if T
Ri
> T
Rs
2 = active if T
Ri
< T
Rs
3 = active if T
Ri
<> T
Rs
0 to 3
1
SP204
20
Room temperature input scanning time HK2 / [min]
1 to 100
1
SP205
0
HK2 room temperature correction in K
-6.0 to +6.0
0.1
SP206
0
Return temperature recording T
RF2
0 = Return temperature not being recorded
1 = T
RF2
is recorded up to max. return temperature limit
2 = T
RF2
for maintaining return temperature
0 to 2
1
SP207
0
TR
F2
correction in K
-10.0 to +10.0
1
SP208
40
Proportional band PI – actuator 2 control in K
2 to 1000
1
SP209
240
Reset time PI – actuator 2 control in seconds
5 to 1000
1
SP210
180
Actuator 2 run-time in seconds
30 to 960
15
SP211
5
Minimum T
F
limit for heating 2 in °C
5 to 100
1
SP212
75
Maximum T
F
limit for heating 2 in °C
20 to 150
1
SP213
5
Intervention level in control of fi nal control element 2 if limit for T
RF2
[K/K] exceeded
0.1 to 10
0.1
SP214
5
Intervention level on T
F2
in K/min if fl ow rate/performance limit excee-
ded
0.0 to 30.0
0.1
SP215
1.2
Slope of heating characteristic for heating 2 in K/K
0.2 to 5.0
0.1
SP216
0.0
External heat portion for heating 2 / [K]
0.0 to 5.0
0.1
SP217
1
Heating medium pump follow-up factor for HK2 (follow-up time / [min]
= fi nal control element run-time x follow-up factor)
1 to 10
1
SP218
0
Optimised for heating 2
0 = not enabled
1 = enabled
0 to 1
1
SP260
0
Screed curing for heating 2
0 = not active
7d = Function heating performed for HK2
25°C = Function heating performed for HK2
8 = Function aborted
9 = Function successfully completed
0; 7d; 25°C;
8; 9
0; 7d;
25°C;
8; 9
SERVice-Parameter
Tab.2
Содержание equitherm EQJW245
Страница 2: ...2 127 www sauter controls com EQJW245 ...
Страница 6: ...6 127 www sauter controls com EQJW245 Content Table of figures 121 List of tables 123 Index 125 ...
Страница 8: ...8 127 www sauter controls com EQJW245 ...
Страница 10: ...10 127 www sauter controls com EQJW245 ...
Страница 12: ...12 127 www sauter controls com EQJW245 ...
Страница 54: ...54 127 www sauter controls com EQJW245 ...
Страница 78: ...78 127 www sauter controls com EQJW245 ...
Страница 88: ...88 127 www sauter controls com EQJW245 ...
Страница 92: ...92 127 www sauter controls com EQJW245 ...
Страница 102: ...102 127 www sauter controls com EQJW245 ...
Страница 104: ...104 127 www sauter controls com EQJW245 ...
Страница 106: ...106 127 www sauter controls com EQJW245 ...
Страница 108: ...108 127 www sauter controls com EQJW245 ...
Страница 110: ...110 127 www sauter controls com EQJW245 ...
Страница 112: ...112 127 www sauter controls com EQJW245 ...
Страница 122: ...122 127 www sauter controls com EQJW245 ...
Страница 124: ...124 127 www sauter controls com EQJW245 ...