SUNWAY M XS 7500TL
INSTALLATION AND
PROGRAMMING INSTRUCTIONS
98/
148
P081
Range
950 ÷ 1000
0.95 ÷ 1
Instant
Overvoltage
Release Ratio
Default
970
Level
ADVANCED
Address
681
Function
This parameter sets ratio between the trip threshold of the overvoltage
fault and the value at which the overvoltage fault is reset.
P082
Range
1 ÷ 1000
0.001 ÷ 1.000 s
Instant
Overvoltage Trip
Time
Default
5
Level
ADVANCED
Address
682
Function
This is the time during which the instantaneous overvoltage trip condition
must be maintained to prompt the activation of the grid overvoltage fault.
P083
Range
1 ÷ 1000
0.001 ÷ 1.000 s
Instant
Overvoltage
Reset Time
Default
10
Level
ADVANCED
Address
683
Function
This is the time during which the instantaneous overvoltage reset condition
must be maintained to prompt the grid overvoltage fault reset.
P084
Range
105 ÷ 130
[105 ÷ 130] % of Vn
Maximum
Voltage Trip
Threshold
Default
120 (Italy), 110 (Spain), 115 (Germany)
Level
ADVANCED
Address
684
Function
This parameter is expressed as a percentage of the rated grid voltage; it
sets the trip threshold for the grid maximum voltage fault.
P085
Range
900 ÷ 1000
0.900 ÷ 1.000
Maximum
Voltage Release
Ratio
Default
950
Level
ADVANCED
Address
685
Function
Sets the ratio between the trip voltage value for the maximum voltage fault
and the value at which it is reset.
P086
Range
20 ÷ 1000
0.020 ÷ 1.000 s
Maximum
Voltage Trip Time
Default
50 (Italy), 150 (Spain), 150 (Germany)
Level
ADVANCED
Address
686
Function
This is the time during which the maximum voltage trip condition must be
maintained to prompt the activation of the grid maximum voltage fault.