INSTALLATION AND
PROGRAMMING INSTRUCTIONS
SUNWAY M XS 7500TL
91/
148
P021
Range
0 ÷ 6000
0 ÷ 600.0 s
Startup Delay
Default
600
60.0 s
Level
ADVANCED
Address
621
Function
Minimum time when the open-circuit voltage of the PV field must be longer
than the time set in
P020
to enable the inverter startup.
P026
Range
0 ÷ 1
0 : Inactive
1: Active
MPPT
Default
1
1: Active
Level
ADVANCED
Address
626
Function
MPPT Enable: if
P026
= Active, the MPPT (Maximum Power Point
Tracking) is enabled. If
P026
is set to Inactive, the MPPT is in manual
mode and the field voltage reference is the one set in
P020
.
Advanced
Parameters
See Table 18
Power Balance
See Table 20
Reactive Power
See Table 21
Figure 68:Tools menu, Advanced Configuration > Inverter
Menu
ADVANCED PARAMETERS
Submenu
Access
Level
Action
P041 – POWER OFF DELAY
Displays the value currently set for the power
off delay
ADVANCED
Activates an alphanumeric keypad window.
Enter the desired value.
Table 19: Tools menu, Advanced Configuration > Inverter > Advanced Parameters submenu