INSTALLATION AND
PROGRAMMING INSTRUCTIONS
SUNWAY M XS 7500TL
69/
148
M000
Range
0 ÷ 9000
0 ÷ 900.0 V
Field Voltage
Address
1650
Level
BASIC
Function
Field voltage that has been measured.
M001
Range
0 ÷ 9000
0 ÷ 900.0 V
MPPT Reference
Address
1651
Level
ADVANCED
Function
When the inverter is running, this is the measure of the voltage reference
generated by the MPPT; when the inverter is
not
running, this is the
voltage value of the PV field voltage.
M002
Range
0 ÷ 3000
0 ÷ 30.00 A
Field Current
Address
1652
Level
BASIC
Function
Field current that has been measured.
M016
Range
0 ÷ 32767
0 ÷ 32767
Grid KO Event
Counter
Address
1670
Level
ADVANCED
Function
Counter for “weak radiation” events.
M017
Range
0 ÷ 65535
0 ÷ 65.535 MΩ
Positive Pole
Insulation
Resistance
Address
1672
Level
ADVANCED
Function
Insulation resistance of the positive pole of the PV field.
M019
Range
0 ÷ 65535
0 ÷ 65.535 MΩ
Negative Pole
Insulation
Resistance
Address
1673
Level
ADVANCED
Function
Insulation resistance of the negative pole of the PV field.