INSTALLATION AND
PROGRAMMING INSTRUCTIONS
SUNWAY M XS 7500TL
105/
148
I002
Range
0 ÷ 1
0: Inactive
1: Active
Partial Energy
Reset
Default
0
0: Inactive
Level
ADVANCED
Address
1389
Function
Resets the partial active energy meter (
M011)
.
I004
Range
0 ÷ 1
0: Inactive
1: Active
Weak Radiation
Events Reset
Default
0
0: Inactive
Level
ADVANCED
Address
1391
Function
Resets the Radiation KO events counter (
M016)
.
I012
Range
0 ÷ 4
0: No Command
1: Restore Backup
3: Save Work
4: Restore Default
EEPROM
Operations
Default
This is not a parameter: I012 is set to zero at power on and whenever the
command is executed.
Level
ADVANCED
Address
1399
Function
This parameter allows managing the storage and restoration of the whole
set of parameters that can be accessed by the user:
1
:
Restore Backup
: The parameters stored in the Backup zone are
copied and stored to the WORK zone, where they serve as the new RAM
parameterization; the previous data of the Work zone are cleared.
Backup
→
RAM
→
Work.
3
:
Save Work
: The current values of the parameters in the RAM are saved
to the non-volatile memory in the Work zone. All parameters are saved at
a time.
RAM
→
Work.
4
:
Restore Default
: Factory-setting values are restored for all parameters,
and the factory-setting values are stored to the non-volatile memory in the
Work zone.
Default
→
RAM
→
Work.
L011
Range
N/A
Display Reset
Default
N/A
Level
BASIC
Function
This is a command. Enables restarting the touchscreen display.
I030
Range
0 ÷ 1
0: Inactive
1: Active
Test V Min
Default
0
0: Inactive
Level
ADVANCED
Address
1417
Function
This parameter enables testing the activation of the grid minimum voltage
threshold as required by the Italian regulations in force governing Low
Voltage grids.