SUNWAY M XS 7500TL
INSTALLATION AND
PROGRAMMING INSTRUCTIONS
106/
148
I031
Range
0 ÷ 1
0: Inactive
1: Active
Test V Max
Default
0
0: Inactive
Level
ADVANCED
Address
1418
Function
This parameter enables testing the activation of the grid maximum voltage
threshold as required by the Italian regulations in force governing Low
Voltage grids.
I032
Range
0 ÷ 1
0: Inactive
1: Active
Test f Min
Default
0
0: Inactive
Level
ADVANCED
Address
1419
Function
This parameter enables testing the activation of the grid minimum
frequency threshold as required by the Italian regulations in force
governing Low Voltage grids.
I033
Range
0 ÷ 1
0: Inactive
1: Active
Test f Max
Default
0
0: Inactive
Level
ADVANCED
Address
1420
Function
This parameter enables testing the activation of the grid maximum
frequency threshold as required by the Italian regulations in force
governing Low Voltage grids.
L500
Range
N/A
History Reset
Default
N/A
Level
BASIC
Function
This command resets the display history data.
This command permanently deletes the history data saved on the display.
OFF
Range
0 ÷ 1
0: Inactive
1: Active
Inverter Power
Off
Default
0
0
Level
ADVANCED
Address
1406
Function
This parameter powers off the inverter. This parameter may be changed
only if the inverter is not delivering energy.
Press the WAKE UP button to power on the inverter again. Alternatively,
the inverter will automatically power on again when the morning comes.
RST
Range
0, 34
0: No command
34: Reset inverter
Inverter Reset
Default
0
0
Level
ADVANCED
Address
50
Function
This is a command. Resets the control electronics of the inverter without
affecting the touchscreen display functionality.