SUNWAY M XS 7500TL
INSTALLATION AND
PROGRAMMING INSTRUCTIONS
96/
148
Menu
GRID INTERFACE
Submenu
Access Level
Action
P091 – MINIMUM VOLTAGE RESET
TIME
Displays the value currently set for the
parameter
ADVANCED
Activates an alphanumeric keypad window.
Enter the desired value.
This is a view-only parameter. The Service access level is required
for parameter modification.
P092
–
INSTANT GRID
UNDERVOLTAGE THRESHOLD
Displays the value currently set for the
parameter
ADVANCED
Activates an alphanumeric keypad window.
Enter the desired value.
This is a view-only parameter. The Service access level is required
for parameter modification.
P093 – INSTANT UNDERVOLTAGE
RELEASE RATIO
Displays the value currently set for the
parameter
ADVANCED
Activates an alphanumeric keypad window.
Enter the desired value.
This is a view-only parameter. The Service access level is required
for parameter modification.
P094 – INSTANT UNDERVOLTAGE
TRIP TIME
Displays the value currently set for the
parameter
ADVANCED
Activates an alphanumeric keypad window.
Enter the desired value.
This is a view-only parameter. The Service access level is required
for parameter modification.
P095 – INSTANT UNDERVOLTAGE
RESET TIME
Displays the value currently set for the
parameter
ADVANCED
Activates an alphanumeric keypad window.
Enter the desired value.
This is a view-only parameter. The Service access level is required
for parameter modification.
P096 – MAXIMUM FREQUENCY TRIP
THRESHOLD
Displays the value currently set for the
parameter
ADVANCED
Activates an alphanumeric keypad window.
Enter the desired value.
This is a view-only parameter. The Service access level is required
for parameter modification.
P097
–
MAXIMUM FREQUENCY
RELEASE RATIO
Displays the value currently set for the
parameter
ADVANCED
Activates an alphanumeric keypad window.
Enter the desired value.
This is a view-only parameter. The Service access level is required
for parameter modification.
P098 – MAXIMUM FREQUENCY TRIP
TIME
Displays the value currently set for the
parameter
ADVANCED
Activates an alphanumeric keypad window.
Enter the desired value.
This is a view-only parameter. The Service access level is required
for parameter modification.
P099 – MAXIMUM FREQUENCY RESET
TIME
Displays the value currently set for the
parameter
ADVANCED
Activates an alphanumeric keypad window.
Enter the desired value.
This is a view-only parameter. The Service access level is required
for parameter modification.
P100 – MINIMUM FREQUENCY TRIP
THRESHOLD
Displays the value currently set for the
parameter
ADVANCED
Activates an alphanumeric keypad window.
Enter the desired value.
This is a view-only parameter. The Service access level is required
for parameter modification.
P101
–
MINIMUM
FREQUENCY
RELEASE RATIO
Displays the value currently set for the
parameter
ADVANCED
Activates an alphanumeric keypad window.
Enter the desired value.
This is a view-only parameter. The Service access level is required
for parameter modification.
P102 – MINIMUM FREQUENCY TRIP
TIME
Displays the value currently set for the
parameter
ADVANCED
Activates an alphanumeric keypad window.
Enter the desired value.
This is a view-only parameter. The Service access level is required
for parameter modification.
P103 – MINIMUM FREQUENCY RESET
TIME
Displays the value currently set for the
parameter
ADVANCED
Activates an alphanumeric keypad window.
Enter the desired value.
This is a view-only parameter. The Service access level is required
for parameter modification.