INSTALLATION AND
PROGRAMMING INSTRUCTIONS
74/
148
M005
Range
± 10000
± 100.00 Hz
Grid Frequency
Address
1655
Level
BASIC
Function
Grid frequency that has been measured.
M006
Range
4600TL: 0 ÷ 3000
5000TL: 0 ÷ 3000
6000TL: 0 ÷ 3000
7500TL: 0 ÷ 4000
4600TL: 0 ÷ 30.00 A
5000TL: 0 ÷ 30.00 A
6000TL: 0 ÷ 30.00 A
7500TL: 0 ÷ 40.00 A
Grid Current
Address
1656
Level
BASIC
Function
Current delivered to the grid.
MPWR
Range
4600TL: 0 ÷ 5000
5000TL: 0 ÷ 6000
6000TL: 0 ÷ 7000
7500TL: 0 ÷ 8000
4600TL: 0 ÷ 5000 W
5000TL: 0 ÷ 6000 W
6000TL: 0 ÷ 7000 W
7500TL: 0 ÷ 8000 W
Grid Power
Address
1658
Level
BASIC
Function
Active power delivered to the grid.
M010
Range
0 ÷ 4294967296
0 ÷ 42949672.96 kWh
Total Energy
Address
1661-1662
Level
BASIC
Function
Total count of the active energy delivered to the grid.
M011
Range
0 ÷ 4294967296
0 ÷ 42949672.96 kWh
Partial Energy
Address
1663-1664
Level
BASIC
Function
Partial count of the active energy delivered to the grid. This value is reset
when the
I002
command is run (4.3.5.4).
M200
Range
0 ÷ 4294967296
0 ÷ 429496729.6 Euros
Total Pay-off
Address
1807, 1808
Level
BASIC
Function
This measure represents the total pay-off resulting from the total count of
the energy delivered to the grid (
M010
).
The remuneration factor is set via parameter
P130
(4.3.5.1).
M201
Range
0 ÷ 4294967296
0 ÷ 429496729.6 Euros
Partial Pay-off
Address
1809, 1810
Level
BASIC
Function
This measure represents the partial pay-off resulting from the total count
of the energy delivered to the grid (
M011
). This value is reset when the
I002
command is run (4.3.5.4).